Appendix 1 –Ratings and Heat Loss Comparison

PL.F7.05 Page

27

of 54

NEC HP Ratings for 230V Normal Duty Models


GPD506/P5 230V Models

F7 240V Models

Variable

Torque

(n116=1)

Normal Duty

(C6-01=2)

NEC

HP

230V

NEC

Amps

GPD506/P5

Model

CIMR-P5U

Output

Amps

Fc

kHz

Overload%

VT

1 minute

F7

Model

CIMR-F7U

Output

Amps

Fc

kHz

Overload %

ND

1 minute

0.5 2.2 20P41 3.2

15 120

0.75 3.2

20P41 3.6 10 107

1 4.2 20P71 6.0

15 120 20P71 4.6 10 107

1.5 6

2 6.8 21P51 8.0

15 120

21P51 7.8 10 108

3 9.6 22P21 11

15 120 22P21 10.8 8 107

5 15.2 23P71 17.5

15 120 23P71 16.8 10 107

7.5 22 25P51 27

10 120 25P51 23 15 120

10 28 27P51 36

10 120 27P51 31 15 102

15 42 20111 54

10 120 20111 46.2 8 117

20 54

20151 59.4 10 117

25 68 20151 68

10 120 20181 74.8 10 114

30 80 20181 80

15 120 20221 88 10 116

40 104 20221 104

15 120 20301 115 10 120

50 130 20301 130

10 120

60 154 20371 160

10 120

20371 162 5 107

75 192 20451 192

10 120 20451 192 5 113

20551 215 8 120

100 248 20551 248 8

120

125 312 20751 312 8

120

20751 312 2 109

150 360

- -

- - 20901 360 2 115

150 360

- -

- - 21100 415 2 120