Appendix 3- Parameter Cross Reference

PL.F7.05 Page

39

of 54

GPD506/P5 Parameter

F7 Parameter

Param

No.

Nxxx

Parameter

Name

Description or Selection

Description or Selection

Parameter

Name

Param.

No.

to all frequency reference sources.

033

Rated motor current


Set unit: 0.1A (In 1000A or more, every 1A)
Set range:10-200% of drive rated current

Set to the motor nameplate full load current
in amperes (A). This value is automatically
set during Auto-Tuning.

Motor Rated Current

E2-01

034

Motor protection selection
(OL1)

0: Disabled.
1: Standard motor (eight minutes)
2: Standard motor (five minutes)
3: Inverter rated motor (eight minutes)
4: Inverter rated motor (five minutes)

Sets the motor thermal overload protection
(OL1) based on the cooling capacity of the
motor.
0: Disabled
1: Standard Fan Cooled (< 10:1 motor)
2: Standard Blower Cooled (

≥10:1 motor)

3: Vector Motor (

≤1000:1 motor)

Motor Overload Protection
Selection

L1-01

035

Cooling fin overheat
Stop method
selection

0: Deceleration stop
(Decelerate by deceleration time 1)
1: Coast to stop
2: Deceleration stop
(Decelerate by deceleration time 2)
3: Operation continues
(The alarm is displayed, and drive runs at
80% of the freq ref)

Selects the Drive operation upon an OH
pre-alarm detection.
0: Ramp to Stop
1: Coast to Stop

2: Fast-Stop
3: Alarm Only

Overheat Pre-Alarm
Operation Selection

L8-03

036

Multi-function
contact input 1
(terminal S2)

0: REV command (2wire sequence selection)
1: FWD/REV Command
(3wire sequence selection)
2: External fault. (N.O contact input)
3: External fault. (N.C contact input)
4: Fault reset
5: LOCAL/REMOTE switch
(run and freq ref)
6: Communication/Control circuit terminal
switch (run and freq ref)
7: Emergency stop (N.O. contact input)
8: Emergency stop (N.C contact input)
9: FV/FI terminal switch
10: Multistep speed set 1
11: Multistep speed set 2
12: Multistep speed set 3
13: Jog frequency select
14: Accel/decel time switch
15: External base block instruction
(N.O.contact input)
16: External base block instruction
(N.C contact input)
17: Speed search command from Max
frequency
18: Speed search command from set
frequency
19: Parameter set enable/disable
20: PID integral value reset
21: PID control disable
22: Timer start command
23: Inverter overheat
(blinking display of OH3)
24: Sample/holding of analog reference
25: KEB instruction (N.O. contact)
26: KEB instruction (N.C. contact)
27: Decel/accel prohibit
28: PID input characteristic switchover

Terminal S2 is not
programmable in F7 :
F7 default setting for terminal
S2:

Reverse run when closed,
stopped when open.

Initialization parameter
A1-03 programs terminals
S1 and S2 for 2-Wire or
3-Wire run control.

-







037


Multi-function
contact input 2
(terminal S3)







Set range: 2-28
(It is the same as constant n036)









0 to 78
Selects the function of terminal S3.
0: 3-wire control
FWD/REV selection for 3-wire
sequence.
1: Local/Remote Selection
2: Option/Inv Selection
Selects source of frequency reference and
sequence. Closed = Option Card,
Open = b1-01 & b1-02.
3: Multi-Step Frequency Reference 1
4: Multi-Step Frequency Reference 2

Multi-Function Digital Input
Terminal S3 Function
Selection








H1-01