Product Transition Guide

Terminal Comparison

PL.F7.05 Page

17

of 54

GPD506/P5 Terminal

F7 Terminal

(Designations similar to GPD506/P5)

Type

GPD506/P5

Terminal

Default Function & Description

F7

Terminal

Default Function

F7 Description

MC

Fault when closed between
terminals MA and MC
Fault when open between
terminals MB and MC
Multi-function contact output
(n041)
Dry contact capacity:
250VAC 1A or less
30VDC 1A or less

MC

1 A max. at 250Vac
1 A max. at 30Vdc

AM

Frequency meter output
0 to +10V/100% frequency
Multi-function analog monitor 1
(n052)
0 to +10V
2mA or less

FM

Output frequency

0 to +10Vdc or
+/-10Vdc 500 ohm input
10V=100% Output frequency
(Max current 2mA).
4 to 20mA
20mA=100% Output
frequency
Function set by H4-01.

AM

Output current

0 to +10Vdc or
-10 to +10Vdc 500 ohm input
10V=100% Drive output
current (Max current 2mA)
4 to 20mA / 100%
Drive's rated output current /
Function set by H4-04.

Anal

og Out

put

Si

gnal

s

AC

Frequency meter output “AM”
Common

AC

Analog common



RP

Pulse input

1 to 32kHz (3k ohms) ±5%
High level voltages 3.5 to 13.2
Low level voltages 0.0 to 0.8
Duty Cycle (on/off) 30% to
70% Function set by H6-01.

Pulse I/O



MP

Pulse monitor

0 to 32kHz
+5V output
(Load: 1.5k ohms)
Function set by H6-06.

R+

R-

Modbus communication
Differential input,
PHC isolation

S+

S-

Modbus communication
Differential output,
PHC isolation

R

S

-485/

422

IG

Signal common