Appendix 3- Parameter Cross Reference

PL.F7.05 Page

47

of 54

GPD506/P5 Parameter

F7 Parameter

Param

No.

Nxxx

Parameter

Name

Description or Selection

Description or Selection

Parameter

Name

Param.

No.

Selects the number of pulses per second of
the output voltage waveform. Setting range
determined by C6-01 setting.
0: Low noise
1: Fc = 2.0 kHz
2: Fc = 5.0 kHz
3: Fc = 8.0 kHz
4: Fc = 10.0 kHz
5: Fc = 12.5 kHz
6: Fc = 15.0 kHz
F: Program (Determined by the settings of
C6-03 thru C6-05)

Carrier Frequency Selection










C6-02

2.0 to 15.0 kHz

Carrier Frequency Upper
Limit

C6-03

0.4 to 15.0 kHz

Carrier Frequency Lower
Limit

C6-04

054

Carrier frequency

1, 2, 4 ~ 6: carrier freq = set value * 2.5 Khz
3: Carrier frequency =8kHz
7, 8, 9: The output freq of 2.5kHz or less is
proportional to the carrier frequency.
(7: 12*fout ,8: 24*fout, 9:36*fout)
10: Carrier frequency =7kHz
(Only 400V 45kW)

0 to 99

Sets the relationship of output frequency to
carrier frequency when C6-02 = F.

Carrier Frequency
Proportional Gain

C6-05

055

Operation after
momentary power
loss

0: Not Provided.
1: Operation continues after power recovery
within 2 sec
2: Operation continues while control power is
on ( UV1, UV3 faults not are detected)

Enables and disables the momentary power
loss function.
0: Disabled - Drive trips on (UV1) fault
when power is lost.
1: Power Loss Ride Thru Time - Drive will
restart if power returns within the time
set in L2-02.*
2: CPU Power Active - Drive will restart if
power returns prior to control power
supply shut down.*
* In order for a restart to occur, the run
command must be maintained throughout
the ride thru period.

Momentary Power Loss
Detection Selection

L2-01

056

Speed search operation level Set unit: 1%

Set range: 0-200%
(100%= rated current of inverter)

0 to 200
Used only when b3-01 = 2 or 3. Sets the
speed search operation current as a
percentage of Drive rated current.

Speed Search Deactivation
Current

b3-02

057

Minimum base block time

Set unit: 0.1sec
Set range: 0.5-10.0sec

0.1 to 5.0sec
Sets the minimum time to wait to allow the
residual motor voltage to decay before the
Drive output turns back on during power
loss ride thru. After a power loss, if L2-03
is greater than L2-02, operation resumes
after the time set in L2-03.

Momentary Power Loss
Minimum Base Block Time

L2-03

058

V/f during speed
search

Set unit: 1% and set range: 0-100%

-

-

-

059

Power ride through
time

Set unit: 0.1sec and set range: 0.0-2.0sec

0.0 to 25.5sec
Sets the power loss ride-thru time. This
value is dependent on the capacity of the
Drive. Only effective when L2-01 = 1.

Momentary Power Loss
Ride-thru Time

L2-02