Appendix 3- Parameter Cross Reference

PL.F7.05 Page

52

of 54

GPD506/P5 Parameter

F7 Parameter

Param

No.

Nxxx

Parameter

Name

Description or Selection

Description or Selection

Parameter

Name

Param.

No.

096

Energy Saving
Selection

0: Energy saving disabled
1: Energy saving enabled

Energy Savings function enable/disable
selection.
0: Disabled
1: Enabled

Energy Saving Control
Selection

b8-01

097

Energy Saving
Gain K2

Set unit: 0.01 (It is 0.1 units in 100 or more)
Set range: 0.00-655.0
(Energy Saving disabled=0.00)

0.0 to 10.0
Sets energy savings control gain when in
vector control method.

Energy Saving Gain

b8-02

098

Energy Save Voltage Lower
limit @ 60 Hz

Set unit: 1%
Set range: 0-120%

Power Detection Filter Time

b8-05

099

Energy Save Voltage Lower
limit @ 6 Hz

Set unit:1%
Set range:0-25%

Used to fine-tune the energy savings
function when in V/F control method.

Search Operation Voltage
Limit

b8-06

100

Time of average
KW

Set unit:1 (1=25ms)
Set range: 1-200 (25ms=5.0sec)

0 to 2000
Used to fine-tune the energy savings
function when in V/F control method.

Power Detection Filter Time

b8-05

101

MEMOBUS timeout
detection

0: Timeout detection disabled.
1: Timeout detection enabled.

Enables or disables the communications
timeout fault (CE).
0: Disabled - A communication loss will
not cause a communication fault.
1: Enabled - If communication is lost for
more than 2 seconds, a CE fault will
occur.

Communication Fault
Detection Selection

H5-05

102

MEMOBUS Stop
method selection at
communication error (CE)

0: Deceleration stop
(Decelerate by deceleration time 1)
1: Coast stop
2: Deceleration stop
(Decelerate by deceleration time 2)
3: Continue operation (alarm display)

Selects the stopping method when a
communication timeout fault (CE) is
detected.
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only
4: Run at d1-04

Stopping Method After
Communication Error

H5-04

103

MEMOBUS
Frequency reference unit
selection

0: 0.1Hz/1
1: 0.01Hz/1
2: 100%/30000
3: 0.1%/1

104

MEMOBUS
Slave address

Set unit:1 Set range:0-31
(There is no MEMOBUS communication at
set point =0)

0 to 20 Hex
Selects Drive station node number
(address) for Modbus terminals R+, R-, S+,
S-. The Drive’s power must be cycled for
the setting to take effect.

Drive Node Address

H5-01

105

MEMOBUS
Baud rate selection

0: 2400bps
1: 4800bps
2: 9600bps

Selects the baud rate for Modbus terminals
R+, R-, S+ and S-. The Drive’s power must
be cycled for the setting to take effect.
0: 1200 bps
1: 2400 bps
2: 4800 bps
3: 9600 bps
4: 19200 bps

Communication Speed
Selection

H5-02

106

MEMOBUS
Parity selection

0: Parity none
1: Even parity
2: Odd parity

Selects the communication parity for
Modbus terminals R+, R-, S+ and S-. The
Drive’s power must be cycled for the
setting to take effect.
0: No Parity
1: Even Parity
2: Odd Parity

Communication Parity
Selection

H5-03

107

Slip compensation
Gain

Set unit: 0.1%
Set range: 0.0-9.9%
(100%= maximum voltage frequency)

0.0 to 2.5
This parameter is used to increase motor
speed to account for motor slip by boosting
the output frequency.
If the speed is lower than the frequency
reference, increase C3-01.
If the speed is higher than the frequency
reference, decrease C3-01

Slip Compensation Gain






C3-01

108

Motor no-load current

Set unit: 1%
Set range: 0-99%
(100%= rated current of motor)

Set to the magnetizing current of the motor
as a percentage of full load amps (E2-01).
This value is automatically set during
rotational Auto-Tuning.

Motor No-Load Current

E2-03

109

Slip comp Primary
Delay Time Constant

Set unit: 0.1sec
Set range: 0.0-25 and 5sec

0 to 10000
This parameter adjusts the filter on the

Slip Compensation
Primary Delay Time

C3-02