Appendix 3- parameter cross reference, Parameter name – Yaskawa GPD 506/P5 to F7 User Manual

Page 41

Advertising
background image

Appendix 3- Parameter Cross Reference

PL.F7.05 Page

41

of 54

GPD506/P5 Parameter

F7 Parameter

Param

No.

Nxxx

Parameter

Name

Description or Selection

Description or Selection

Parameter

Name

Param.

No.




(con’t)

037


















































Multi-function contact input 2
(terminal S3)






































































Set range: 2-28
(It is the same as constant n036)
































































Open = Only using monitor U1-01 can
be changed.
1C: Trim Control Increase
Closed = Increase frequency reference
By value in d4-02.
Open = Return to normal frequency
reference.
Not effective when “multi-step speed 1
to 4” input is closed. Must be used in
conjunction with Trim Ctrl Decrease.
1D: Trim Control Decrease
Closed = Decrease frequency reference
by value in d4-02
Open = Return to normal frequency
reference.
Not effective when using d1-01 thru
d1-16 as frequency reference. Must be
used in conjunction with Trim Ctrl
Increase.
1E: Reference Sample Hold
Analog frequency reference is sampled
then held at time of input closure.
20: External Fault, Normally Open, Always
Detected, Ramp To Stop
21: External Fault, Normally Closed,
Always Detected, Ramp To Stop
22: External Fault, Normally Open, During
Run, Ramp To Stop
23: External Fault, Normally Closed,
During Run, Ramp To Stop
24: External Fault, Normally Open, Always
Detected, Coast To Stop
25: External Fault, Normally Closed,
Always Detected, Coast To Stop
26: External Fault, Normally Open, During
Run, Coast To Stop
27: External Fault, Normally Closed,
During Run, Coast To Stop
28: External Fault, Normally Open, Always
Detected, Fast-Stop
29: External Fault, Normally Closed,
Always Detected, Fast-Stop
2A: External Fault, Normally Open, During
Run, Fast-Stop
2B: External Fault, Normally Closed,
During Run, Fast-Stop
2C: External Fault, Normally Open,
Always Detected, Alarm Only
2D: External Fault, Normally Closed,
Always Detected, Alarm Only
2E: External Fault, Normally Open, During
Run, Alarm Only
2F: External Fault, Normally Closed,
During Run, Alarm Only
30: PID integral reset
Closed = Set integrator value to 0.
31: PID integral hold
Closed = Hold integrator at its present
level.
32: Multi-Step Reference 4
Based on the status of Multi-Step
Reference 1 to 4 (d1-16).
34: PID Soft Starter Cancel
Closed = b5-17 is ignored.
35: PID Input (Error) Polarity Change
Closed = PID error signal polarity is
reversed (1 to -1 or -1 to 1).
60: DC Injection Braking
Closed = Apply DC injection current as
set in parameter b2-02.









Multi-Function Digital Input
Terminal S3 Function
Selection

































































H1-01