3.3 Selecting Peripheral Devices

3.3

Selecting Peripheral Devices

Selecting Heavy Duty or Standard Duty RC5 Application

The RC5 overload rating has the capability of 150% braking torque for 30 seconds and 200% peak braking torque. The overload capability is based

on the standard duty rating. The RC5 overload rating can be applied to heavy duty applications. The following is a description of the heavy duty and

standard duty ratings.

Heavy Duty

Heavy duty applications require continuous energy dissipation (100% braking torque).
The overload rating is 125% for 60 seconds with a duty cycle of 25%. Braking torque of 187.5% is available for 30 seconds. Please note the peak

torque should be less than 250%.

The RC5 requires selecting Power Coordination and Current Suppression reactors according to specifications in

Table 3.3

.

Standard Duty

Standard duty applications require intermittent full energy dissipation. The continuous rating is 80% or less braking torque and 100% braking torque

for 60 seconds with a duty cycle of 25% (60 seconds maximum on-time of every 240 seconds). The overload rating is 150% braking torque for 30

seconds. Please note the peak torque should be less than 200%.
The RC5 requires selecting Power Coordination and Current Suppression reactors according to specifications in

Table 3.3

Main Circuit Input Fuse

Fuse Kits

The Fuse Kit is sized for both Heavy Duty and Standard Duty applications.

Connect a fuse at the primary side of the power suppression reactor. Recommended fuses are shown in

Table 3.1

and

Table 3.2

.

Table 3.1 200 V Class Input Fuse

Note: These fuses and fuse holders are made by FERRAZ.

RC5

Input fuse

Fuse holder

Model

CIMR-R5U†

Rated

regenerative

capacity (kW)

25%ED

Rated input

current

(Aac)

25%ED

Yaskawa

Part Number

Ferraz

Part Number

Amount

per unit

Yaskawa

Part Number

Ferraz

Part Number

Amount

per unit

23P71A

2.2

10

UFU000151

A30QS20-1

3

UFU000157

70318

1

25P51A

3.7

15

UFU000152

A30QS30-1

3

UFU000157

70318

1

27P51A

5.5

20

UFU000152

A30QS30-1

3

UFU000157

70318

1

20111A

7.5

30

UFU000153

A30QS50-4

3

FU-002082

P243G

3

20151A

11

40

UFU000154

A30QS80-4

3

FU-002083

P243

3

20181A

15

50

UFU000154

A30QS80-4

3

FU-002083

P243

3

20221A

18

60

UFU000155

A30QS100-4

3

FU-002083

P243

3

20301A

22

80

UFU000156

A30QS150-4

3

FU-002083

P243

3

20370A

30

100

UFU000156

A30QS150-4

3

FU-002083

P243

3

Advertising