3 setting the power supply voltage jumper – Yaskawa RC5 Converter User Manual

Page 36

Advertising
background image

36

YASKAWA ELECTRIC TOEP C710656 01C YASKAWA - RC5 Instruction Manual

4.3 Setting the Power Supply Voltage Jumper

4.3

Setting the Power Supply Voltage Jumper

Note: 400 V CLASS REGENERATIVE UNITS OF 37 kW OR HIGHER

Set the power supply voltage jumper for 400 V class power regenerative unit of 37 kW or higher. Insert the jumper into the voltage connector nearest

to the actual power supply voltage.
Incorrect connector setting may negatively impact the performance of the power regenerative unit.
The jumper is factory-set to 460 V when shipped. If the power supply voltage is not 460 V, use the following procedure to change the setting.

1.

Turn OFF the power supply switch and wait for at least five minutes before removing the front panel and setting the jumper.

2.

Remove the front cover.

3.

Insert the jumper at the position for the voltage supplied to the power regenerative unit (see

Figure 4.1

).

4.

Replace the front cover.

Figure 4.1

Figure 4.1 Setting the Power Supply Voltage (For 400 V Class Power Regenerative Unit between 37 kW and 75 kW)

400/415V

21CN

380V

440V

460V

23CN 24CN 25CN 26CN 22CN FU2

20CN TB2

r

Jumper

Advertising