Refer to, Table a.3, Table a.4 – Yaskawa RC5 Converter User Manual

Page 65

Advertising
background image

YASKAWA ELECTRIC TOEP C710656 01C YASKAWA - RC5 Instruction Manual

65

Table A.3 Multi-function Input Functions

Table A.4 Multi-function Output Functions

Setting Value

Function

(H1-01, 02)

Remarks

8

External baseblock (NO contact)

[Ext BaseBlk N.O.]

9

External baseblock (NC contact)

[Ext BaseBlk N.C.]

F

Not used

[Term Not Used]

14

Fault reset

[Fault Reset]

24-2F

External fault

[External Fault]

24: External Fault, Normally Open, Always Detected, Coast To Stop

25: External Fault, Normally Closed, Always Detected, Coast To Stop

26: External Fault, Normally Open, During Run, Coast To Stop

27: External Fault, Normally Closed, During Run, Coast To Stop

28: External Fault, Normally Open, Always Detected, Fast Stop

29: External Fault, Normally Closed, Always Detected, Fast Stop

2A: External Fault, Normally Open, During Run, Fast Stop

2B: External Fault, Normally Closed, During Run, Fast Stop

2C: External Fault, Normally Open, Always Detected, Alarm Only

2D: External Fault, Normally Closed, Always Detected, Alarm Only

2E: External Fault, Normally Open, During Run, Alarm Only

2F: External Fault, Normally Closed, During Run, Alarm Only

Setting value

Function

(H2-02, 03)

Remarks

0

During run

[During RUN 1]

Closed = When a run command is input or the Unit is outputting voltage.

6

Regenerative unit ready

[Regen Unit Ready]

Closed = When the Unit is powered up, not in a fault state, and in the DRIVE

mode.

7

During DC bus undervoltage (UV) detection

[DC Bus Undervolt]

Closed = When the DC bus voltage falls below the UV trip level set in L2-05.

8

During baseblock

[BaseBlk 1]

Closed = When the Unit is not outputting voltage.

A

During MCON

[Mc On]

Closed = When the pre-charge contactor contact is energized.

E

Fault

[Fault]

Closed = When the Unit experiences a major fault.

F

Not used

[Not Used]

10

Alarm

[Minor Fault]

Closed = When the Unit experiences an alarm.

11

Fault reset command active

[Reset Cmd Active]

Closed = When the Unit receives a reset command from a digital input terminal or

serial communication.

1E

Restart enabled

[Restart Enabled]

Closed = When the Unit is performing an automatic restart attempt. Automatic

restart is configured by parameter L5-01.

1F

Overload (OL1) pre-alarm

[Overload (OL1)]

Closed = When OL1 is 80% of its trip point or greater.

20

Overheat pre-alarm

[OH Prealarm]

Closed = When the Unit’s heatsink temperature exceeds the setting of parameter

L8-02.