3.4 Wiring Main Circuit Terminals

YASKAWA ELECTRIC TOEP C710656 01C YASKAWA - RC5 Instruction Manual

31

Closed-Loop Connectors Size

Yaskawa recommends using closed-loop crimp terminals.
UL/cUL approval requires the use of closed-loop crimp terminals when wiring the main circuit terminals.
Use only the tools recommended by the terminal manufacturer for crimping.

Table 3.6 Closed Loop Connectors Sizes (JIS C 2805) (For 200 V/400 V classes)

Note: Determine the wire size for the main circuit so that line voltage drop is within 2% of the rated voltage. Line voltage drop is calculated as follows:

(If there is a possibility of excessive voltage drop, use a larger wire suitable to the required length.)

Line voltage drop (V) = 3 x wire resistance (

Ω/km) x wire length (m) x current (A) x 10

-3

Wire Size

Terminal Screw

Tightening Torque (N•m)

Closed Loop Connectors

mm

2

AWG

0.5

20

M3.5

M4

0.8 to 1.0
1.2 to 1.4

R1.25-3.5

R1.25-4

0.75

18

1.25

16

2

14

M4

1.2 to 1.4

R2-4

M5

2.1 to 2.5

R2-5

3.5

12

M4

1.2 to 1.4

3.5-4

M5

2.1 to 2.5

3.5-R5

5.5

10

M4

1.2 to 1.4

R5.5-4

M5

2.1 to 2.5

R5.5-5

8

8

M5

2.1 to 2.5

R8-5

M6

3.6 to 5.1

R8-6

14

6

M6

3.6 to 5.1

R14-6

22

4

M8

8.2 to 10.2

R22-8

30/38

3/2

M8

8.2 to 10.2

R38-8

30/38

3/2

M10

18 to 23

R38-10

50/60

1/1/0

R60-10

80

3/0

R80-10

100

4/0

R100-10

100

4/0

M12

31.5 to 39.5

R100-12

150

300

R150-12

200

400

R200-13