4.6 Power On/Off Sequence

YASKAWA ELECTRIC TOEP C710656 01C YASKAWA - RC5 Instruction Manual

43

4.6

Power On/Off Sequence

Refer to

Figure 4.5

when building a power ON/OFF sequence for the RC5.

Figure 4.5

Figure 4.5 Power Supply ON/OFF Sequence

Check the following when using the power regenerative unit.

• Run commands of the drive and the power regenerative unit should be turned ON after confirming that the drive and the power regenerative unit

are READY.

• Run commands of the drive and the power regenerative unit should be turned ON at the same time.

• Never turn the run command of the power regenerative unit OFF while the drive output during run is ON.

• Run output of the power regenerative unit turns OFF one second after the run command is turned OFF.

• Turn the power OFF after the run output of the power regenerative unit is OFF.

AC Power Supply

READY

Drive

READY

Run Command

Output during Run

Power Regenerative Unit

Output Frequency

1 sec

STOP

RUN

STOP

RUN

F

F

O

N

O

STOP

RUN

STOP

RUN

DC Injection Braking

OFF

OFF

ON

ON

Power Regenerative Unit

Drive

Drive

Run Command

Power Regenerative Unit

Output during Run

Drive