4.6 Power On/Off Sequence
YASKAWA ELECTRIC TOEP C710656 01C YASKAWA - RC5 Instruction Manual
43
4.6
Power On/Off Sequence
when building a power ON/OFF sequence for the RC5.
Figure 4.5
Figure 4.5 Power Supply ON/OFF Sequence
Check the following when using the power regenerative unit.
• Run commands of the drive and the power regenerative unit should be turned ON after confirming that the drive and the power regenerative unit
are READY.
• Run commands of the drive and the power regenerative unit should be turned ON at the same time.
• Never turn the run command of the power regenerative unit OFF while the drive output during run is ON.
• Run output of the power regenerative unit turns OFF one second after the run command is turned OFF.
• Turn the power OFF after the run output of the power regenerative unit is OFF.