6.1 Fault Detection

YASKAWA ELECTRIC TOEP C710656 01C YASKAWA - RC5 Instruction Manual

51

OL
Input Over Loaded

Power Regenerative Unit Input
Overload
Power regenerative unit input exceeded
the overload capacity.

The load is too heavy.

Check the size of the load.

EF3
External Fault 3

External fault
(terminal S3-SC)

An external fault was input from a
multi-function input.

• Reset external fault inputs to the

multi-function inputs.

• Remove the cause of the external

fault.

EF4
External Fault 4

External fault
(terminal S4-SC)

OPR
Oper Disconnect

Operator Connection Fault
The Operator was disconnected during
operation started by a run command
from the Operator.

Check the Operator connection.

ERR
EEPROM R/W Err

EEPROM Write Error

A verification error occurred when
writing EEPROM.
Try turning the power supply off and on
again.
Try setting the constants again.

CPF00
COM-ERR (OP&CONV)

Control Circuit Error 1
(Operator Communications Error)

• Communications with the digital

operator were not established within 5
seconds after the power was turned
on.

• MPU peripheral element check fault.

• Disconnect the digital operator and

then connect it again.

• Check the wiring of the control circuit

power supply.

• Replace the control card.

CPF01
COM-ERR (OP&CONV)

Control Circuit Error 2
(Operator Communications Error)

• After communications were

established, there was a transmission
error with the digital operator for
more than 2 seconds.

• MPU peripheral element check fault

• Disconnect the digital operator and

then connect it again.

• Check the wiring of the control circuit

power supply.

• Replace the control card.

CPF02
BB Circuit Err

Baseblock Circuit Error

The control circuit is damaged.

Replace the control card.

CPF03
EEPROM Err

EEPROM Error

CPF04
Internal A/D Err

CPU Internal A/D Converter Error

Fault Display

Meaning

Probable Causes

Corrective Actions