Error Code

Name

Description

1004

Response to select before operate does not
match

The select response message received from the slave
module is not that expected from the last select
request. This indicates a synchronization problem
between the master and slave devices.

1005

Response does not contain date/time object

The response message from the slave device does not
contain a date/time object. The master expects this
object for the response message.

1006

Time-out condition on response

The slave device did not respond to the last request
message from the master within the time-out set for the
IED device. The application layer time-out value is
specified for each IED unit in the slave configuration
table in the module. This table is established each time
the module performs the restart operation.

1007

Function code in application layer message not
supported

The function code returned in the response message is
not valid for the application layer or not supported by
the module.

1008

Read operation not supported for
object/variation

The application layer response message contains an
object that does not support the read function.

1009

Operate function not supported for the
object/variation

The application layer response message contains an
object that does not support the operate function.

1010

Write operation not supported for the
object/variation

The application layer response message contains an
object that does not support the write function.

5.7

DNP Configuration Forms

This section contains a configuration form to be used when designing an
application.

5.7.1 MVI46-DNP

Communication Module Configuration

[Section]/Item Value

Range

Description

[MODULE]

General module configuration section

Module Name:

0 to 80 characters This parameter assigns a name to the module that can

be viewed using the configuration/debug port. Use this
parameter to identify the module and the configuration
file.


[Section]/Item Value

Range

Description

[DNP Slave]

DNP Slave configuration information

Internal Slave ID:

0 to 65534

This is the DNP address for the module. All messages
with this address from the master will be processed by
the module.

Baud Rate:

Baud rate value Primary DNP Port Baud Rate: 300, 600, 1200, 2400,

4800, 9600, 19200, 384 (38400) , 576 (57600), 115
(115200)

RTS On:

0 to 65535
milliseconds

This value represents the number of 1 ms increments to
be inserted between asserting the RTS modem line and
the actual transmission of the data.