Module error codes – 60 word error list, 2 module error codes – 60 word error list – ProSoft Technology MVI46-DNP User Manual

Page 97

Advertising
background image

Reference MVI46-DNP

♦ SLC Platform

Master/Slave Communication Module

ProSoft Technology, Inc.

Page 97 of 143

August 23, 2007

Example Address Word

Data Address Variable Name

Description

N11:53

53

M1: .1589

DNP Master Length
Error Count (Physical
Layer Error)

This value counts the number of times an
invalid length byte is received. If the length of
the message does not match the length value in
the message, this error occurs.

N11:54

54

M1: .1590

DNP Master Bad CRC
Error Count (Physical
Layer Error)

This value counts the number of times a bad
CRC value is received in a message.

N11:55 N11:56

55 to 56 M1: .1591 M1:

.1592

Program Scan Counter This value is incremented each time a program

scan occurs in the module. The double-word
value can be used to determine if the module is
functioning and at what rate.

N11:57 N11:58

57 to 58 M1: .1593 M1:

.1594

Free Memory

This value indicates the amount of memory
available in the unit. This memory is located in
the far heap of the module.

N11:59

59

M1: .1595

Reserved

Future Use

N11:60 to N11:119 60 to 119 M1: .1596 to

M1: .1655

Error List Data

Error List of log. The following topic contains a
complete list of error codes returned here.

N11:120 120

M1:

.1656

Floating-point

Input

Event Count

This value represents the number of event
messages generated from the Floating-point
input database.

N11:121

121

M1: .1657

Double Floating-point
Input Event Count

This value represents the number of event
messages generated from the double input
database.

N11:122

122

M1: .1658

Number of Event
Messages to Send to
Processor from Master
Driver

This value represents the number of event
messages waiting to be processed.

N11:123

123

M1: .1659

Event Message Buffer
Overflow

This flag will be set to 1 if the event message
buffer overflows. If the value is set to 0, the
buffer is not overflowed.

N11:124 to
N11:159

124 to
159

M1: .1669 to M1:
.1695

Reserved

Reserved for future use.

5.6.2 Module Error Codes – 60 Word Error List

If the module's program encounters an error during execution, it will log the error
to the error list. This list is transferred to the M1: file in elements 1596 to 1655.
The SLC ladder logic should be programmed to transfer this M1: file data to a
data table in the SLC. The tables below list the error codes generated by the
program with their associated description. Use the errors to help determine
where problems exist in the system.