ProSoft Technology MVI46-DNP User Manual
Page 118

MVI46-DNP ♦ SLC Platform
Reference
Master/Slave Communication Module
Page 118 of 143
ProSoft Technology, Inc.
August 23, 2007
Object
Request
Response
Obj Var Description
Func
Codes
Qual
Codes
(hex)
Func
Codes
Qual
Codes
(hex)
Data
Size
(bits)
Notes
40 0 Analog
Output
Status - All
Variations
1
06
24
Slave will return
variation 2 data
1
32-Bit Analog
Output Status
1
06
129,130
00,01
40
Slave will return this
variation but data
only 16-bit accuracy
2
16-Bit Analog
Output Status
1
06
129, 130
00, 01
24
Slave will return this
variation
41 0 Analog
Output
Block - All
Variations
24
Slave will respond
to this request using
variation 2 data
1
32-Bit Analog
Output Block
3, 4, 5, 6 17, 28
129,130
00,01
40
Slave will respond
to this request but
data only 16-bit
2
16-Bit Analog
Output Block
3, 4, 5, 6 17, 28
129
Echo of
Request
24
Slave will respond
to this request
50
0
Time and Date -
All Variations
2
07, With
Quant=1
48
Slave will use
variation 1
1
Time and Date
2
07, With
Quant=1
48
Slave will respond
to this variation
2
Time and Date
With Interval
80
Slave will return
Unknown Object to
this request
51
0
Time and Date
CTO - All
Variations
Slave will return
Unknown Object to
this request
1
Time and Date
CTO
129, 130
07, With
Quant=1
48
Slave will return
Unknown Object to
this request
2
Unsynchronized
Time and Date
CTO
129, 130
07, With
Quant=1
48
Slave will return
Unknown Object to
this request
52
0
Time Delay - All
Variations
1
Time Delay
Coarse
129
07, With
Quant=1
16
Slave will never
return this variation
2
Time Delay Fine
129
07, With
Quant=1
16
Slave will return this
variation to
functions 0D, 0E,
and 17
60
0
Not Defined
Not Defined in DNP
1
Class 0 Data
1
06
Slave will respond
to this variation will
all static data
2
Class 1 Data
1
06, 07,
08
Slave will respond
to this variation (No
class 1 data defined
in application)