ProSoft Technology MVI46-DNP User Manual

Page 66

Advertising
background image

MVI46-DNP ♦ SLC Platform

Reference

Master/Slave Communication Module

Page 66 of 143

ProSoft Technology, Inc.

August 23, 2007

The following table describes the format of the M0: file used by the module:

M0: File Configuration

Offset Max

Elements

Description

0 to 73

74

Reserved

80 to 299

220

Control Block

300 to 420

121

Event Message Data (121 Words of Data)

421 to 3799

3379

Reserved for Future Use

This file contains 3800 elements, and its composition is discussed in the
configuration (page 17) section of this document.

The M1: file stores DNP and IED data. The following table describes the format
of this file:

M1: File Configuration

Offset

Max Elements

Description

Max Pnts

0 to 127

128

DNP Binary Inputs

2048

128 to 383

256

DNP Analog Inputs

256

384 to 511

128

DNP Counters

64

512 to 639

128

DNP Binary Outputs

2048 (1024 Trip/Close)

640 to 767

128

DNP Analog Outputs

128

768 to 895

128

IED Binary Inputs

2048

896 to 1151

256

IED Analog Inputs

256

1152 to 1279

128

IED Counters

64

1280 to 1407

128

IED Binary Outputs

2048

1408 to 1535

128

IED Analog Outputs

128

1536 to 1595

60

Error/Status Data

N/A

1596 to 1695

100

Error List and Status Data

N/A

1696 to 1823

128

DNP Float Input

64

1824 to 1951

128

Reserved

32

1952 to 2079

128

DNP Float Output

64

2080 to 2207

128

Reserved

32

This file contains 2207 elements with a fixed memory location for each data type.

The following table describes the relationship between the SLC data files and the
DNP and IED memory areas in the module's M1: file.

SLC Files

M1: File Data
DNP Memory

DNP Master Device

Digital Input File

Digital Input Data

Analog Input File

Analog Input Data

Counter Data File

Counter Data

Digital Output File

Digital Output Data

Analog Output File

Analog Output Data

Advertising