The following table describes the format of the M0: file used by the module:
M0: File Configuration
Offset Max
Elements
Description
0 to 73
74
Reserved
80 to 299
220
Control Block
300 to 420
121
Event Message Data (121 Words of Data)
421 to 3799
3379
Reserved for Future Use
This file contains 3800 elements, and its composition is discussed in the
configuration (page 17) section of this document.
The M1: file stores DNP and IED data. The following table describes the format
of this file:
M1: File Configuration
Offset
Max Elements
Description
Max Pnts
0 to 127
128
DNP Binary Inputs
2048
128 to 383
256
DNP Analog Inputs
256
384 to 511
128
DNP Counters
64
512 to 639
128
DNP Binary Outputs
2048 (1024 Trip/Close)
640 to 767
128
DNP Analog Outputs
128
768 to 895
128
IED Binary Inputs
2048
896 to 1151
256
IED Analog Inputs
256
1152 to 1279
128
IED Counters
64
1280 to 1407
128
IED Binary Outputs
2048
1408 to 1535
128
IED Analog Outputs
128
1536 to 1595
60
Error/Status Data
N/A
1596 to 1695
100
Error List and Status Data
N/A
1696 to 1823
128
DNP Float Input
64
1824 to 1951
128
Reserved
32
1952 to 2079
128
DNP Float Output
64
2080 to 2207
128
Reserved
32
This file contains 2207 elements with a fixed memory location for each data type.
The following table describes the relationship between the SLC data files and the
DNP and IED memory areas in the module's M1: file.
SLC Files
M1: File Data
DNP Memory
DNP Master Device
Digital Input File
→
→
Digital Input Data
Analog Input File
→
→
Analog Input Data
Counter Data File
→
→
Counter Data
Digital Output File
←
←
Digital Output Data
Analog Output File
←
←
Analog Output Data