August 23, 2007

Object

Request

Response

Obj Var Description

Func
Codes

Qual
Codes
(hex)

Func
Codes

Qual
Codes
(hex)

Data
Size
(bits)

Notes

2

16-Bit Binary
Counter

129, 130

00, 01

24

Slave will return
Unknown Object to
this request

3

32-Bit Delta
Counter

129, 130

00, 01

40

Slave will return
Unknown Object to
this request

4

16-Bit Delta
Counter

129, 130

00, 01

24

Slave will return
Unknown Object to
this request

5

32-Bit Binary
Counter Without
Flag

1, 7, 8,
9, 10

06

129, 130

00, 01

32

Slave will return this
variation

6

16-Bit Binary
Counter Without
Flag

1, 7, 8,
9, 10

06

129, 130

00, 01

16

Slave will return this
variation (counter
upper 16-bits
removed)

7

32-Bit Delta
Counter Without
Flag

129, 130

00, 01

32

Slave will return
Unknown Object to
this request

8

16-Bit Delta
Counter Without
Flag

129, 130

00, 01

16

Slave will return
Unknown Object to
this request

21

0

Frozen Counter -
All Variations

1

06

32

Slave will return
variation 9 data

1

32-Bit Frozen
Counter

129, 130

00, 01

40

Slave will return
Unknown Object to
this request

2

16-Bit Frozen
Counter

129, 130

00, 01

24

Slave will return
Unknown Object to
this request

3

32-Bit Frozen
Delta Counter

40

Slave will return
Unknown Object to
this request

4

16-Bit Frozen
Delta Counter

24

Slave will return
Unknown Object to
this request

5

32-Bit Frozen
Counter With
Time Of Freeze

88

Slave will return
Unknown Object to
this request

6

16-Bit Frozen
Counter With
Time Of Freeze

72

Slave will return
Unknown Object to
this request

7

32-Bit Frozen
Delta Counter
With Time Of
Freeze

88

Slave will return
Unknown Object to
this request

Advertising