Poll interval, Uploading and downloading the configuration file, Transferring the configuration file to your pc – ProSoft Technology MVI46-DNP User Manual

Page 30

Advertising
background image

MVI46-DNP ♦ SLC Platform

Configuring the Module

Master/Slave Communication Module

Page 30 of 143

ProSoft Technology, Inc.

August 23, 2007

Poll Interval

This parameter specifies the minimum frequency at which the module should
execute the command. The value is entered in units of seconds. For example, to
execute a command every 10 seconds, enter a value of 10 in the field. A value of
0 for the parameter implies that the command should be executed every scan of
the list.

2.4

Uploading and Downloading the Configuration File

ProSoft modules are shipped with a pre-loaded configuration file. In order to edit
this file, you must transfer the file from the module to your PC. After editing, you
must transfer the file back to the module.

This section describes these procedures.

Important:

The illustrations of configuration/debug menus in this section are intended

as a general guide, and may not exactly match the configuration/debug menus in your
own module. For specific information about the configuration/debug menus in your
module, refer to The Configuration/Debug Menu (page 39).

2.4.1 Transferring the Configuration File to Your PC

1

Connect your PC to the Configuration/Debug port of the module using a
terminal program such as HyperTerminal. Press [?] to display the main
menu.