ProSoft Technology MVI46-DNP User Manual
Page 121

Reference MVI46-DNP
♦ SLC Platform
Master/Slave Communication Module
ProSoft Technology, Inc.
Page 121 of 143
August 23, 2007
Object
Request
Response
Obj Var Description
Func
Codes
Qual
Codes
(hex)
Func
Codes
Qual
Codes
(hex)
Data
Size
(bits)
Notes
1
Binary Input Change
Without Time
1 06,
07,
08
129, 130
17, 28
8
Master will
generate and
process this
variation.
2
Binary Input Change
With Time
1 06,
07,
08
129, 130
17, 28
56
Master will
generate and
process this
variation.
3
Binary Input Change
With Relative Time
1 06,
07,
08
129, 130
17, 28
24
Master will
generate and
process this
variation.
10
0
Binary Output - All
Variations
1
06
8
1
Binary Output
1
2
Binary Output
Status
129, 130
00, 01
8
Master does not
use this object
type and will not
generate a
message or
process this
type.
12
0
Control Block - All
Variations
88
1
Control Relay
Output Block
3, 4, 5, 6 17, 28
129
Echo of
request
88 Master
will
generate this
variation and
parse the
response.
2
Pattern Control
Block
88
3
Pattern Mask
16
20
0
Binary Counter - All
Variations
1, 7, 8,
9, 10
06
32
Master will
generate this
variation.
1
32-Bit Binary
Counter
129, 130
00, 01
40
Master will
process this
variation.
2
16-Bit Binary
Counter
129, 130
00, 01
24
Master will
process this
variation.
3
32-Bit Delta Counter
129, 130
00, 01
40
Master will
process this
variation.
4
16-Bit Delta Counter
129, 130
00, 01
24
Master will
process this
variation.
5
32-Bit Binary
Counter Without
Flag
1, 7, 8,
9, 10
06
129, 130
00, 01
32
Master will
generate and
process this
variation.