[Section]/Item Value

Range

Description

[IED Database]

Database definition for DNP master port if utilized

Binary Inputs:

0 to 2048 points Number of binary input points contained in the IED

database to transfer to the SLC processor and obtained
from the attached IED units.

Analog Inputs:

0 to 256 points Number of analog input points contained in the IED

database to transfer to the SLC processor and obtained
from the attached IED units.

Counters:

0 to 64 points

Number of counter points contained in the IED
database to transfer to the SLC processor and obtained
from the attached IED units.

Binary Outputs:

0 to 2048 points Number of binary output points contained in the IED

database which are transferred from the SLC processor
and used by the attached IED units.

Analog Outputs:

0 to 128 points Number of analog output points contained in the IED

database which are transferred from the SLC processor
and used by the attached IED units.


[Section]/Item

Description

[DNP Master Slave List]

Definition of the IED units to be interfaced with the DNP
master port if utilized

# This section stores information about each slave to be used by the master port. There must be an
# entry in this table for each node to be used in the command list. Two of the parameters in this list are coded
# values:
# Conf Mode ==> 0=Never, 1=Sometimes and 2=Always (select 0).
# Flags is bit coded as follows:
# Bit 0 (decimal 1) ==> Enable the slave
# Bit 1 (decimal 2) ==> Use Unsolicited messaging with this slave
# Bit 2 (decimal 4) ==> Use delay measurement with this slave
# Bit 3 (decimal 8) ==> Auto time synchronization enabled
#
# Node DL Conf Conf Conf App Rsp
# Address Mode Timeout Retry Timeout Flags
START
END

[Section]/Item

Description

[DNP Master Commands]

Definition of the commands to be issued to the IED
units by the DNP master port.

# This section contains the list of commands to process on the master port.
# Node addresses present in the command list must have an entry in the
# [DNP Slave List]. Commands with nodes not present in the list will not be
# executed.
# 1 2 3 4 5 6 7 8 9 10
#Flags/ Node Data Data Cmd Device Point DNP DB IED DB Poll
#Enable Address Object Variation Func Address Count Address Address interval
START
END