ProSoft Technology MVI46-DNP User Manual

Page 105

Advertising
background image

Reference MVI46-DNP

♦ SLC Platform

Master/Slave Communication Module

ProSoft Technology, Inc.

Page 105 of 143

August 23, 2007

[Section]/Item Value

Range

Description

Analog Outputs:

0 to 128 points Number of analog output points to configure in the DNP

slave device. Each point will occupy a one word area in
the module memory.

PLC Analog Outputs:

0 to 128 points Number of analog output points configured above that

are to be sent to the SLC processor. All other analog
output points will be sent to the attached IED units.

Float Outputs:

0 to 64 points

Number of floating-point output points to configure in
the DNP slave device. Each point will occupy a two-
word area in the module memory.

PLC Float Outputs:

0 to 64 points

Number of floating-point output points configured above
that are to be sent to the SLC.

[Section]/Item

Description

[DNP Slave Binary Inputs]

DNP database binary input override values

# This area is to override the class assignment for binary input database points. Enter list of points between the
# START and END labels.

#

# Point# Class

START

END

[Section]/Item

Description

[DNP Slave Analog Inputs]

DNP database analog input override values

START

# This area is to override the class and deadband assignment for analog input database points. Enter list of points
# between the START and END labels.

#

# Point# Class Deadband

START

END

[Section]/Item

Description

[DNP Slave Float Inputs]

DNP database floating-point input override values

# This area is to override the class and deadband assignment for float input database points. Enter list of points
# between the START and END labels.

#

# Point# Class Deadband

START

END