[Section]/Item Value
Range
Description
Analog Outputs:
0 to 128 points Number of analog output points to configure in the DNP
slave device. Each point will occupy a one word area in
the module memory.
PLC Analog Outputs:
0 to 128 points Number of analog output points configured above that
are to be sent to the SLC processor. All other analog
output points will be sent to the attached IED units.
Float Outputs:
0 to 64 points
Number of floating-point output points to configure in
the DNP slave device. Each point will occupy a two-
word area in the module memory.
PLC Float Outputs:
0 to 64 points
Number of floating-point output points configured above
that are to be sent to the SLC.
[Section]/Item
Description
[DNP Slave Binary Inputs]
DNP database binary input override values
# This area is to override the class assignment for binary input database points. Enter list of points between the
# START and END labels.
#
# Point# Class
START
END
[Section]/Item
Description
[DNP Slave Analog Inputs]
DNP database analog input override values
START
# This area is to override the class and deadband assignment for analog input database points. Enter list of points
# between the START and END labels.
#
# Point# Class Deadband
START
END
[Section]/Item
Description
[DNP Slave Float Inputs]
DNP database floating-point input override values
# This area is to override the class and deadband assignment for float input database points. Enter list of points
# between the START and END labels.
#
# Point# Class Deadband
START
END