ProSoft Technology MVI46-DNP User Manual

Page 115

Advertising
background image

Reference MVI46-DNP

♦ SLC Platform

Master/Slave Communication Module

ProSoft Technology, Inc.

Page 115 of 143

August 23, 2007

Object

Request

Response

Obj Var Description

Func
Codes

Qual
Codes
(hex)

Func
Codes

Qual
Codes
(hex)

Data
Size
(bits)

Notes

8

16-Bit Frozen
Delta Counter
With Time Of
Freeze

72

Slave will return
Unknown Object to
this request

9

32-Bit Frozen
Counter Without
Flag

1

06

129, 130

00, 01

32

Slave will return this
variation

10

16-Bit Frozen
Counter Without
Flag

1

06

129, 130

00, 01

16

Slave will return this
variation (counter
upper 16-bits
removed)

11

32-Bit Frozen
Delta Counter
Without Flag

32

Slave will return
Unknown Object to
this request

12

16-Bit Frozen
Delta Counter
Without Flag

16

Slave will return
Unknown Object to
this request

22 0 Counter

Change

Event - All
Variations

1 06,

07,

08

Slave will parse this
request and return
no data

1

32-Bit Counter
Change Event
Without Time

129, 130

17, 28

40

Slave will return
Unknown Object to
this request

2

16-Bit Counter
Change Event
Without Time

129, 130

17, 28

24

Slave will return
Unknown Object to
this request

3

32-Bit Delta
Counter Change
Event Without
Time

40

Slave will return
Unknown Object to
this request

4

16-Bit Delta
Counter Change
Event Without
Time

24

Slave will return
Unknown Object to
this request

5

32-Bit Counter
Change Event
With Time

88

Slave will return
Unknown Object to
this request

6

16-Bit Counter
Change Event
With Time

72

Slave will return
Unknown Object to
this request

7

32-Bit Delta
Counter Change
Event With Time

88

Slave will return
Unknown Object to
this request

8

16-Bit Delta
Counter Change
Event With Time

72

Slave will return
Unknown Object to
this request

23 0 Frozen

Counter

Event - All
Variations

Slave will return
Unknown Object to
this request

Advertising