Binary output command examples – ProSoft Technology MVI46-DNP User Manual

Page 24

Advertising
background image

MVI46-DNP ♦ SLC Platform

Configuring the Module

Master/Slave Communication Module

Page 24 of 143

ProSoft Technology, Inc.

August 23, 2007

Port/Flg

Slave

Object

Var

Func

Addr Pnt Cnt DNP DB IED DB Poll Int

WORD

0

1

2

3

4

5

6

7

8

9

VALUE

14

15

1

0

1

0

-32

200

0

2

DNP BI's

IED #15

Address

Address

200

0

231

31

IED BI's

Address

0

NOTE:

Data accessible by remote

DNP master and PLC. Events for
points generated by module. All IED

31

generated events are ignored.

Command for Port 2, Enabled, RBE Flag Set.
IED Unit 15 is to be polled.
Object type is 1 (Binary Input).
Variation of 0 (default variation).
Function 1 is for a read.
Slave address ignored (Qual 6, all points).
Point count of -32 indicates only first 32 points are to
be used.
DNP DB address of 200 is where first data point is
placed.
IED DB address of 0 is where first data point is
placed.
Poll command every 2-seconds.

BINARY OUTPUT COMMAND EXAMPLES:

Port/Flg

Slave

Object

Var

Func

Addr Pnt Cnt DNP DB IED DB Poll Int

WORD

0

1

2

3

4

5

6

7

8

9

VALUE

14

15

12

1

5

10

2

200

0

0

IED #15

DNP BO's

Address

Address

10

200

11

201

Command for Port 2, Enabled, only operate on
point change & use DNP Database.
IED Unit 15 is to be polled.
Object type is 12 (Binary Output Control).
Variation of 1 (Control Relay Output Block).
Function 5 is for direct operate.
Slave address of 10 is starting point in IED.
Two points are to be transferred.
DNP DB address of 200 is first source point.
IED DB is not used.
Command not a polled command.

Port/Flg

Slave

Object

Var

Func

Addr Pnt Cnt DNP DB IED DB Poll Int

WORD

0

1

2

3

4

5

6

7

8

9

VALUE

30

15

12

1

5

10

1

0

25

0

IED #15

IED BO's

Address

Address

10

25

Command for Port 2, Enabled, only operate on
point change & use IED Database.
IED Unit 15 is to be polled.
Object type is 12 (Binary Output Control).
Variation of 1 (Control Relay Output Block).
Function 5 is for direct operate.
Slave address of 10 is starting point in IED.
One point is transferred.
DNP DB is not used.
IED DB address of 25 is first source point.
Command not a polled command.