ProSoft Technology PTQ-104C User Manual

Page 47

Advertising
background image

49TPTQ-104C ♦ 48TQuantum Platform

Module Configuration

47TIEC 60870-5-104 Client

12TUser Manual

Type ID Type

Description

Data representation

7

M_BO_NA_1

(7.3.1.7)

Monitored Bitstring of 32-bit data --This data

type stores 32-bit data in binary form. Each bit

in the string has a value of 0 or 1. Associated

time-tagged event information for this type are

M_BO_TA_1 (8) and M_BO_TB_1 (33).

Each of the 32 bits in the bitstring has a

value of 0 or 1 (7.2.6.13).

9

M_ME_NA_1

(7.3.1.9)

Monitored Normalized Measured Value: This

data type is used for analog input data.

Associated time-tagged event information for

this type are M_ME_TA_1 (10) and

M_ME_TD_1 (34).

Normalized values (7.2.6.6) are stored in

a word (16-bit) data area with a range of -

1..+1-2

-15

11

M_ME_NB_1

(7.3.1.11)

Monitored Scaled Measured Value --This data

type is used for analog input data. Associated

time-tagged event information for this type are

M_ME_TB_1 (12) and M_ME_TE_1 (35).

Scaled values (7.2.6.7) are stored in a

word (16-bit) data area with a range of -

2

15

.. +2

15

-1

13

M_ME_NC_1

(7.3.1.13)

Monitored Measured Value, Short Floating-

Point Number: This data type is used for

analog input data stored in floating point

format according to the IEEE STD 754, QDS

format. Associated time-tagged event

information for this type are M_ME_TC_1 (14)

and M_ME_TE_1 (36).

Short floating-point number stored in IEEE

STD 754 format (Fraction, Exponent,

Sign) (7.2.6.8)

15

M_IT_NA_1

(7.3.1.15)

Monitored Integrated Total-point Information --

This data type stores meter or other count

data. Associated time-tagged event

information for this type are M_IT_TA_1 (15)

and M_IT_TB_1 (37).

Binary counter data (7.2.6.9) is stored in a

double-word (32-bit) value with a range of

-2

31

..+2

31

-1.

45

C_SC_NA_1

(7.3.2.1)

Single-point Command: This command

controls a single binary point such as a relay.

Single bit value (7.2.6.15) with 0 = Off and

1 = On

46

C_DC_NA_1

(7.3.2.2)

Double-point Command: This command

controls a dual-point binary control device

such as a trip/close relay.

Double Command (7.2.6.16) with 0 = Not

permitted 1 = Off 2 = On 3 = Not

permitted

47

C_RC_NA_1

(7.3.2.3)

Regulating Step Command: This command

controls a stepping device such as a

transformer.

Regulating Step Command (7.2.6.17) with

0 = Not permitted 1 = Next step lower 2 =

Next step higher 3 = Not permitted

48

C_SE_NA_1

(7.3.2.4)

Setpoint Command, Normalized Value: This

command controls an analog device.

Normalized values (7.2.6.6) are stored in

a word (16-bit)data area with a range of -

1..+1-2

-15

49

C_SE_NB_1

(7.3.2.5)

Setpoint Command, Scaled Value: This

command controls an analog device.

Scaled values (7.2.6.7) are stored in a

word (16-bit) data area with a range of -

2

15

.. +2

15

-1

50

C_SE_NC_1

(7.3.2.6)

Setpoint Command, Short Floating-Point

Format: This command controls an analog

device accepting an IEEE STD 754 floating-

point format value.

Short floating-point number stored in IEEE

STD 754 format (Fraction, Exponent,

Sign) (7.2.6.8)

51

C_BO_NA_1

(7.3.2.7)

Setpoint Command, 32-bit Bitstring: This

command controls a bitstring in a device.

Each of the 32 bits in the bitstring has a

value of 0 or 1 (7.2.6.13).

100

C_IC_NA_1

Group interrogation command

NA

101

C_CI_NA_1

Counter interrogation command

NA

102

C_RD_NA_1

Read command

NA

103

C_CS_NA_1

Clock Synchronization

NA

105

C_RP_NA_1

Reset process command

NA

107

C_TS_TA_1

Test command (104 standard)

NA

110

P_ME_NA_1

Parameter, normalized measured value

Word address

ProSoft Technology, Inc.

Page 47 of 136

March 4, 2013

Advertising