ProSoft Technology PTQ-104C User Manual
Page 47

49TPTQ-104C ♦ 48TQuantum Platform
Module Configuration
47TIEC 60870-5-104 Client
12TUser Manual
Type ID Type
Description
Data representation
7
M_BO_NA_1
(7.3.1.7)
Monitored Bitstring of 32-bit data --This data
type stores 32-bit data in binary form. Each bit
in the string has a value of 0 or 1. Associated
time-tagged event information for this type are
M_BO_TA_1 (8) and M_BO_TB_1 (33).
Each of the 32 bits in the bitstring has a
value of 0 or 1 (7.2.6.13).
9
M_ME_NA_1
(7.3.1.9)
Monitored Normalized Measured Value: This
data type is used for analog input data.
Associated time-tagged event information for
this type are M_ME_TA_1 (10) and
M_ME_TD_1 (34).
Normalized values (7.2.6.6) are stored in
a word (16-bit) data area with a range of -
1..+1-2
-15
11
M_ME_NB_1
(7.3.1.11)
Monitored Scaled Measured Value --This data
type is used for analog input data. Associated
time-tagged event information for this type are
M_ME_TB_1 (12) and M_ME_TE_1 (35).
Scaled values (7.2.6.7) are stored in a
word (16-bit) data area with a range of -
2
15
.. +2
15
-1
13
M_ME_NC_1
(7.3.1.13)
Monitored Measured Value, Short Floating-
Point Number: This data type is used for
analog input data stored in floating point
format according to the IEEE STD 754, QDS
format. Associated time-tagged event
information for this type are M_ME_TC_1 (14)
and M_ME_TE_1 (36).
Short floating-point number stored in IEEE
STD 754 format (Fraction, Exponent,
Sign) (7.2.6.8)
15
M_IT_NA_1
(7.3.1.15)
Monitored Integrated Total-point Information --
This data type stores meter or other count
data. Associated time-tagged event
information for this type are M_IT_TA_1 (15)
and M_IT_TB_1 (37).
Binary counter data (7.2.6.9) is stored in a
double-word (32-bit) value with a range of
-2
31
..+2
31
-1.
45
C_SC_NA_1
(7.3.2.1)
Single-point Command: This command
controls a single binary point such as a relay.
Single bit value (7.2.6.15) with 0 = Off and
1 = On
46
C_DC_NA_1
(7.3.2.2)
Double-point Command: This command
controls a dual-point binary control device
such as a trip/close relay.
Double Command (7.2.6.16) with 0 = Not
permitted 1 = Off 2 = On 3 = Not
permitted
47
C_RC_NA_1
(7.3.2.3)
Regulating Step Command: This command
controls a stepping device such as a
transformer.
Regulating Step Command (7.2.6.17) with
0 = Not permitted 1 = Next step lower 2 =
Next step higher 3 = Not permitted
48
C_SE_NA_1
(7.3.2.4)
Setpoint Command, Normalized Value: This
command controls an analog device.
Normalized values (7.2.6.6) are stored in
a word (16-bit)data area with a range of -
1..+1-2
-15
49
C_SE_NB_1
(7.3.2.5)
Setpoint Command, Scaled Value: This
command controls an analog device.
Scaled values (7.2.6.7) are stored in a
word (16-bit) data area with a range of -
2
15
.. +2
15
-1
50
C_SE_NC_1
(7.3.2.6)
Setpoint Command, Short Floating-Point
Format: This command controls an analog
device accepting an IEEE STD 754 floating-
point format value.
Short floating-point number stored in IEEE
STD 754 format (Fraction, Exponent,
Sign) (7.2.6.8)
51
C_BO_NA_1
(7.3.2.7)
Setpoint Command, 32-bit Bitstring: This
command controls a bitstring in a device.
Each of the 32 bits in the bitstring has a
value of 0 or 1 (7.2.6.13).
100
C_IC_NA_1
Group interrogation command
NA
101
C_CI_NA_1
Counter interrogation command
NA
102
C_RD_NA_1
Read command
NA
103
C_CS_NA_1
Clock Synchronization
NA
105
C_RP_NA_1
Reset process command
NA
107
C_TS_TA_1
Test command (104 standard)
NA
110
P_ME_NA_1
Parameter, normalized measured value
Word address
ProSoft Technology, Inc.
Page 47 of 136
March 4, 2013