ProSoft Technology PTQ-104C User Manual

Page 66

Advertising
background image

Module Configuration

49TPTQ-104C ♦ 48TQuantum Platform

12TUser Manual

47TIEC 60870-5-104 Client


Bitstring: double-word-addressing
Setpoint normalized: word-addressing
Setpoint scaled: word-addressing
Setpoint floating: double-word-addressing
Parameter normalized: word-addressing
Parameter scaled: word-addressing
Parameter float: double-word-address
Integrated BCD: 3-word-addressing

5.6.4 [IEC-104 Client/Session x > IEC-104 Client x Sector 1] section

This section defines Sector 1 of Session x.

Item

Range

Description

Common ASDU
Address

0 to 65535

This parameter sets the common ASDU address
to associate with this sector of the specified
session.

Online Time Sync

Y or N

This parameter specifies if the sector in the
controlled device will be sent a time
synchronization command when the unit is first
recognized as being online.

Online General Int

Y or N

This parameter specifies if the sector in the
controlled device will be sent a general
interrogation command when the unit is first
recognized as being online.