Item

Range

Description

EOI Time Sync

Y or N

This parameter specifies if the sector in the
controlled device will be sent a time
synchronization command after this module
receives an EOI message from the controlled unit.

EOI General Int

Y or N

This parameter specifies if the sector in the
controlled device will be sent a general
interrogation command after this module receives
an EOI message from the controlled unit.

Use Time Tag
Commands

Y or N

This parameter specifies if a time tag field is to be
included with commands. This is as specified in
the IEC-870-5-104 specification and should only
be utilized if the controlled device supports these
new data types. If the parameter is set to Y, a time
tag will be added to all commands. If the
parameter is set to N, the normal IEC-870-5-101
data type messages will be utilized

5.6.5 [IEC-104 Client/Session x > IEC-104 Client x Sector 1] section

This section defines the Data Type distribution of the module database for Client
x Sector 1.