ProSoft Technology PTQ-104C User Manual

Page 63

Advertising
background image

49TPTQ-104C ♦ 48TQuantum Platform

Module Configuration

47TIEC 60870-5-104 Client

12TUser Manual

5.6.1 [IEC-104 Client/Session x > IEC-104 Client x] section

Item

Range

Description

Server IP Address

IP dotted
notation

IP address for the server to connect this client to
with 0.0.0.0 used to disable the client.

Sector Count

1 or 2

This parameter sets the number of sectors
contained in this controlled device. The range of
values is from 1 to 2. A sector section is required
for each sector in a session to define its database
and settings.

T0 timeout

1 to 30

Number of seconds to wait for connection to be
established with server in seconds (default=30)

T1 timeout

1 to 255

Number of seconds until a timeout occurs to send
or test APDU's (Application Protocol Data Units)
(default = 15)

T2 timeout

1 to 255

Number of seconds until timeout for non-data
acknowledgement (t2 < t1) (default=10)

T3 timeout

1 to 300

Timeout for test frame on idle state in seconds
(default=20)

k (maximum queue)

1 to 12

Maximum number of messages to hold in queue

w (latest ack threshold)

1 to 8

Threshold value when to send ack. This
parameter should be less than or equal to two-
thirds of k.

Originator address for
COT

0 to 255

Originator address in the COT (Cause of
Transmission) to use in all messages from the
client

Response Timeout

500 to 2^32-1

This parameter sets the maximum number of
milliseconds to wait for a confirmation from the
controlled station to a request from this module to
application level messages.

ProSoft Technology, Inc.

Page 63 of 136

March 4, 2013

Advertising