8 [ethernet configuration] section, 9 to create optional comment entries, Ethernet configuration] section – ProSoft Technology PTQ-104C User Manual
Page 73: To create optional comment entries, Ethernet configuration

49TPTQ-104C ♦ 48TQuantum Platform
Module Configuration
47TIEC 60870-5-104 Client
12TUser Manual
Data Type
Description
Qualifier Parameter
110
111
112
Word address, Normalized measured
value
Word address, Scaled measured value
Float (double-word), Short float value
The following applies to Type 110, 111,
112:
Type of parameter:
0=Not used
1=Threshold value
2=Smoothing factor (filter time constant)
3=Low limit for transmission of measured
values
4=High limit for transmission of
measured values
5 to 31 = Reserved by standard
32 to 63 = Reserved for special use
(private range)
Local parameter change:
0=No change
64=Change
Parameter in operation:
0=Operation
128=Not in operation
113
*Word address, Activation command
Parameter Qualifier:
0=Not used
1=Act/Deact of previously loaded
parameters (point index = 0)
2=Act/Deact of the parameter of the point
index specified
3=Act/Deact of persistent cyclic or
periodic transmission of the addressed
object
4 to 127 = Reserved by standard
128 to 255 = Reserved for special use
(private range)
Activation Qualifier:
0=Deactivate
256=Activate
5.8
[Ethernet Configuration] section
See page 19 for more information.
5.9
To Create Optional Comment Entries
1 Click the plus sign to the left of the
icon to expand the module
Comments.
ProSoft Technology, Inc.
Page 73 of 136