1 led status indicators, 1 ethernet led indicators, Led status indicators – ProSoft Technology PTQ-104C User Manual

Page 94: Ethernet led indicators, Led indicators

Advertising
background image

Diagnostics and Troubleshooting

49TPTQ-104C ♦ 48TQuantum Platform

12TUser Manual

47TIEC 60870-5-104 Client


8.1

LED Status Indicators

LED

Color

Status

Description

PRT1

Green

On

Data is being transferred between the module and a remote
terminal using the Configuration/Debug port.

Off

No data is being transferred on the Configuration/Debug port.

PRT2

Green

On

Port not used in application

Off

Port not used in application

PRT3

Green

On

Port not used in application

Off

Port not used in application

ERR1

Red

Off

The PTQ-104C is working normally.

On

The PTQ-104C module program has recognized an application
error.

ERR2

N/A

Not used in application

ERR3

Red

On

Configuration Error

Active

Green

On

The LED is on when the module recognizes a processor and is
able to communicate if the [Backplane Data Movement] section
specifies data transfer commands.

Off

The LED is off when the module is unable to communicate with the
processor. The processor either absent or not running.

BAT

Red

Off

The battery voltage is OK and functioning.

On

The battery voltage is low or the battery is not present. The battery
LED will illuminate briefly upon the first installation of the module or
if the unit has been un-powered for an extended period of time.
This behavior is normal, however should the LED come on in a
working installation please contact ProSoft Technology.

If the module is not operating and the status LEDs are not illustrated in the table
above, please call ProSoft Technology for technical assistance.

8.1.1 Ethernet LED Indicators

LED

State

Description

Data

Off

No activity on the Ethernet port.

Green Flash

The Ethernet port is actively transmitting or receiving data.

Link

Off

No physical network connection is detected. No Ethernet
communication is possible. Check wiring and cables.

Green Solid

Physical network connection detected. This LED must be on
solid for Ethernet communication to be possible.

Page 94 of 136

ProSoft Technology, Inc.

March 4, 2013

Advertising