Module Configuration

49TPTQ-104C ♦ 48TQuantum Platform

12TUser Manual

47TIEC 60870-5-104 Client


Item

Range

Description

Data Type

ASDU Type

This parameter is used to set the ASDU data
type to be used with the message. The codes
specified are those defined for the IEC-870-5-
101 protocol. The following is a listing of
command control data types supported in this
module:

Type: 45, 46, 47, 48, 49, 50, 51, 100, 101, 102,
103, 105, 107, 110, 111, 112, 113. (Full
descriptions on page 46)

Point Index

1 to 65535

This parameter is the value for the Information
Object Address (IOA) in the target device

Qualifier

1 to 1023

This parameter is dependent on the Data Type
selected. See below for details.

Qualifier Parameter configuration

The Qualifier Parameter is based on a combination of parameters each with their
own value, based on the Type used in the command. The corresponding
parameters for each Data Type have a numerical code assigned to them. The
Qualifier Parameter value is the sum of these numerical codes.

Data Type

Description

Qualifier Parameter

45

Bit address, Single point command

Single Point Value:

0=Off

1=On

46

Bit address, Double point command

Double Point Value:

0=Not permitted

1=Off

2=On

3=Not Permitted

47

Byte address, Regulating step point
command

Regulating Point Value:

0=Not permitted

1=Next step lower if database point is set to -1

2=Next step high if database point set to +1

3=Not Permitted

The following parameters apply to each Data Type (45, 46, 47)

Qualifier Code

0=No additional definition (slave dependent)

4=Short pulse duration

8=Long pulse duration

12=Persistent output

Select/Execute

0=Direct execution without select

128=Select executed followed by execute

256=Deselect command

Page 70 of 136