2 time zone, 3 use daylight savings time, 4 database register – ProSoft Technology PTQ-104C User Manual

Page 61: 5 [iec-104 client module, Time zone, Use daylight savings time, Database register, Iec-104 client module

Advertising
background image

49TPTQ-104C ♦ 48TQuantum Platform

Module Configuration

47TIEC 60870-5-104 Client

12TUser Manual

5.4.2 Time Zone

-11 to 11

This parameter specifies the time zone offset to be used from the UTC time
zone. A value of zero uses UTC time. If the value entered is positive, the time
zone is west of the UTC time zone (that is, Eastern Standard Time is 5). If the
value entered is negative, the time zone is east of the UTC time zone (that is,
Continental Europe is -1).

5.4.3 Use Daylight Savings Time

Yes or No

This parameter specifies if daylight savings time will be used in the time
computation.

5.4.4 Database Register

-1 or 0 to 3992 as an even value

This parameter specifies if the NTP time computed by the driver is to be placed
into the module’s database. If a value of -1 is specified, the time will not be
placed into the database. If the value is between 0 and 3992, the time will be
placed in the database. The first 4 bytes will represent the seconds since
1/1/1970, and the second 4 bytes will represent the number of microseconds. An
even value should be used for the register value in order for the data to be stored
correctly.

5.5

[IEC-104 Client Module]

The [IEC-104 Client Module] section of PCB includes the general configuration of
the 104C driver.

ProSoft Technology, Inc.

Page 61 of 136