ProSoft Technology PTQ-104C User Manual

Page 64

Advertising
background image

Module Configuration

49TPTQ-104C ♦ 48TQuantum Platform

12TUser Manual

47TIEC 60870-5-104 Client


ACTTERM with
setpoint

Y or N

This parameter specifies what the last message
will be in the response to a setpoint command. If
the parameter is set to Y, an ACTTERM will be
the last response. If set to N, ACTCON will be the
last response.

Status Offset

-1 to 3956

-1: Disable

0-3956: Database location of client status data

NOTE: requires 44 registers and should be placed
in a location of the module memory that is being
used for read data to transfer this information
back to the processor.

5.6.2 [IEC-104 Client/Session x > IEC-104 Client x Sector 0] section

Item

Range

Description

Common ASDU
Address

0 to 65535

This parameter sets the common ASDU address
to associate with this sector of the specified
session.

Online Time Sync

Y or N

This parameter specifies if the sector in the
controlled device will be sent a time
synchronization command when the unit is first
recognized as being online.

Online General Int

Y or N

This parameter specifies if the sector in the
controlled device will be sent a general
interrogation command when the unit is first
recognized as being online.

EOI Time Sync

Y or N

This parameter specifies if the sector in the
controlled device will be sent a time
synchronization command after this module
receives an EOI message from the controlled unit.

Page 64 of 136

ProSoft Technology, Inc.

March 4, 2013