ProSoft Technology PTQ-104C User Manual

Page 65

Advertising
background image

49TPTQ-104C ♦ 48TQuantum Platform

Module Configuration

47TIEC 60870-5-104 Client

12TUser Manual

EOI General Int

Y or N

This parameter specifies if the sector in the
controlled device will be sent a general
interrogation command after this module receives
an EOI message from the controlled unit.

Use Time Tag
Commands

Y or N

This parameter specifies if a time tag field is to be
included with commands. This is as specified in
the IEC-870-5-104 specification and should only
be utilized if the controlled device supports these
new data types. If the parameter is set to Y, a time
tag will be added to all commands. If the
parameter is set to N, the normal IEC-870-5-101
data type messages will be utilized

5.6.3 [IEC-104 Client/Session x > IEC-104 Client x Sector 0] section

This section defines the Data Type distribution of the module database for Client
x Sector 0.

Item

Range

Description

Data Type

ASDU type code in message

Point Index

0 to 65535

Value for the Information Object Address (IOA)

Database Address

0 to 64000

Database address in the module associated to
this point according to ASDU type:

Single-point: bit-addressing
Double-point: bit-addressing
Step-point: byte-addressing

ProSoft Technology, Inc.

Page 65 of 136

March 4, 2013