49TPTQ-104C ♦ 48TQuantum Platform

Module Configuration

47TIEC 60870-5-104 Client

12TUser Manual

5.3.7 Get Module Date and Time Block (9970)

Block 9970 requests the module’s date and time. This data can be used to set
the PLC clock.

5.3.8 Set Module Time Block (9971)

Block identification code 9971 is used to pass the clock time in the PLC to the
module. The date and time provided will be used to set the module’s clock.

Block Format from Processor (4x Register Data) to module

Word Offset in Block

Data Field(s)

Description

0

Sequence
Counter

This field contains a new value each time the user
wishes to request a new command block.

1

Block ID

This field contains the block identification code of 9971
for the block.

2

Year

This field contains the four-digit year for the new time
value.

3

Month

This field contains the month value for the new time.
Valid entry for this field is in the range of 1 to 12.

4

Day

This field contains the day value for the new time. Valid
entry for this field is in the range of 1 to 31.

5

Hour

This field contains the hour value for the new time.
Valid entry for this field is in the range of 0 to 23.

6

Minute

This field contains the minute value for the new time.
Valid entry for this field is in the range of 0 to 59.

7

Seconds

This field contains the second value for the new time.
Valid entry for this field is in the range of 0 to 59.

8

Milliseconds

This field contains the millisecond value for the new
time. Valid entry for this field is in the range of 0 to 999.

9 to 63

Spare

Not Used

Block Format from Module (3x Register Data) to Processor

Word Offset in Block

Data Field(s)

Description

0

Sequence
Counter

This field contains a new value each time the block is
handled.

1

Block ID

This field contains the block identification code of 9971
for the block.

2 to 63

Spare

Not Used

5.3.9 Cold Boot Block (9999)

Block 9999 performs a cold-boot operation on the module. The following table
describes the format of the block constructed by the processor.

Offset

Description

Length

0

9999

1

1 to 63

Spare

63

The warm and cold boot processes perform the same operation. Many of the
variables that must be initialized are fixed when the module first boots. They
cannot be changed after the application starts.

ProSoft Technology, Inc.

Page 59 of 136

March 4, 2013