ProSoft Technology PTQ-104C User Manual

Page 48

Advertising
background image

Module Configuration

49TPTQ-104C ♦ 48TQuantum Platform

12TUser Manual

47TIEC 60870-5-104 Client


Type ID Type

Description

Data representation

111

P_ME_NB_1

Parameter, scaled measured value

Word address

112

P_ME_NC_1

Parameter, short float value

Double-word address

113

P_AC_NA_1

Parameter activation command

NA

The data addressing is resumed in the following table.

Data

Size

Example

Single Point

1 bit

Address 1600 refers to word 100, bit 1 in database

Dual Point

2 bits

Address 1600 refers to word 100, bits 1 and 2 in database

Step Point

1 byte

Address 200 refers to word 100, lower byte in database

Bitstring 32 bit

2 words

Address 50 refers to word 100 and 101 in database

Normalized Measured Value

1 word

Address 100 refers to word 100 in database

Scaled Measured Value

1 word

Address 100 refers to word 100 in database

Short Float Point Measured Value 2 words

Address 50 refers to words 100 and 101 in database

Integrated Total Point

2 words

Address 50 refers to words 100 and 101 in database

Another important concept to understand is the direction of data transfer for the
different data types with reference to the controller. The following illustration
shows the data types (monitored data) that are transferred from the module to
the processor.

The next diagram shows the movement of control data from the processor to the
module. This data is then sent to the controlled devices on the serial networks.

Write Data

Output Data Types

C_SC_NA_1

C_DC_NA_1
C_RC_NA_1

C_SE_NA_1
C_SE_NB_1

C_SE_NC_1

C_BO_NA_1

Page 48 of 136

ProSoft Technology, Inc.

March 4, 2013