Tubing Length

Refrigerant tubing between the indoor and

outdoor units should be kept as short as

possible.

Select and decide the installation location so

that the length of the refrigerant tubing will be

within the limits given in Table 1-10.

Tubing length (L)

INDOOR
UNIT

OUTDOOR
UNIT

Elevation difference (H)

0711_M_I

Fig. 1-1

Table 1-10

Limit of elevation

difference between

the 2 units

Models

CH2442

CH3642,

CH4242

Tubing Data

Tubing size

Narrow tube

in. (mm)

1/4 (6.35)

3/8 (9.52)

outer dia.

Wide tube

in. (mm)

3/4 (19.05)

3/4 (19.05)

Limit of tubing length

(ft.)

165

165

Outdoor unit is higher

165

165

than indoor unit

(ft.)

Outdoor unit is lower

100

100

than indoor unit

(ft.)

Max. allowable tubing length at shipment (ft.)

100

100

Required additional refrigerant

(oz./ft.)

0.48

*1

0.53

*2

No additional charge of compressor oil is necessary.

*

1

If total tubing length becomes 100 to 165 ft., charge additional refrigerant (R22) by 0.48 oz./ft..

*

2

If total tubing length becomes 100 to 165 ft., charge additional refrigerant (R22) by 0.53 oz./ft..