13. PUMP DOWN

Pump down means collecting all refrigerant gas in the

system back into the outdoor unit without losing ant of

the gas. Pump down is used when the unit is to be

moved or before servicing the refrigerant circuit.

Pump down procedure

Be sure to carry out pump

down with the unit in cooling

mode.

(1)

Connect the low pressure side (wide tube valve

service port) charging hose of the manifold valve

to the service port (B) on the wide tube service

valve.

(2)

Using a hex wrench, turn the narrow tube service

valve clockwise all the way to close the service

valve.

(3)

Press the operation button and start cooling

operation.

(4)

When the low pressure gauge reading falls to

14.2 to 7.1 psi (1 to 0.5 kg/cm

2

), fully close the

wide tube valve stem with a standard screwdriver.

Then quickly stop the unit.

(5)

Disconnect all gauges and hoses, and replace

the bonnets and the valve caps as they were

previously.

(6)

Purge all air remaining inside the tubing before

operating the air conditioner.

CAUTION