9

9

9

9

9

SC

71

S4359146

9-4. Mode Setting

According to function of each system controller, set

SW1 as Fig. 9-5.

(1)

Central control/Remote control mode

Central control mode

System controller is used as central control equip-

ment.

Individual setting by remote controller can be

inhibitted by system controller

Remote control mode

System controller is used as remote controller.

Setting by system controller is inhibitted by other

central control equipments.

(2)

ALL/ZONE mode

ALL mode

All indoor units can be controlled by system control-

ler.

ZONE mode

Indoor units in one of ZONE 1, 2, 3 or 4 can be

controlled by system controller

(3)

Function of system controller is 10 types accord-
ing to combination of central control/remote
control mode and ALL/ZONE mode setting as the
table 9-1.

(4)

Stick the system controller unit label in a con-
spicuous position.

Table 9-1

Central control

Remote control

ALL

1. ALL/Central

6. ALL/Remote

ZONE1

2. ZONE1/Central

7. ZONE1/Remote

ZONE2

3. ZONE2/Central

8. ZONE2/Remote

ZONE3

4. ZONE3/Central

9. ZONE3/Remote

ZONE4

5. ZONE4/Central

10. ZONE4/Remote

2048_M_I

2

ON
OFF

3 4 5 6

ALL

central control

2

ON
OFF

3 4 5 6

ALL

remote control

Inter-unit control wiring

2

ON
OFF

3 4 5 6

ZONE1

central control

2

ON
OFF

3 4 5 6

1

ZONE1

remote control

2

16

ZONE1

central control

address 1-16

2

ON
OFF

3 4 5 6

ZONE2

central control

2

ON
OFF

3 4 5 6

17

ZONE2

remote control

18

32

ZONE2

central control

address 17-32

2

ON
OFF

3 4 5 6

ZONE3

central control

2

ON
OFF

3 4 5 6

33

ZONE3

remote control

34

48

ZONE3

central control

address 33-48

2

ON
OFF

3 4 5 6

ZONE4

central control

2

ON
OFF

3 4 5 6

49

ZONE4

remote control

50

64

ZONE4

central control

address 49-64

Central control

mode

Remote control

mode

Fig. 9-5