TEST RUN

12-1. Preparing for Test Run

Before attempting to start the air conditioner,

check the following:

(1)

All loose matter is removed from the cabinet

especially steel filings, bits of wire, and clips.

(2)

The control wiring is correctly connected and all

electrical connections are tight.

(3)

The protective spacers for the compressor used

for transportation have been removed. If not,

remove them now.

(4)

The transportation pads for the indoor fan have

been removed. If not, remove them now.

(5)

The power has been connected to the unit for at

least 5 hours before starting the compressor. The

bottom of the compressor should be warm to the

touch and the crankcase heater around the feet

of the compressor should be hot to the touch.

(Fig. 12-1)

(6)

Both the wide and narrow tube service valves are

open. If not, open them now. (Fig. 12-2)

Test run procedure

The purpose of the test run function is to let you control the operation of the unit directly without the

thermostat turning the unit on or off. As indicated in the following procedure, switch out of TEST

RUN when you are finished, or the air conditioner can be damaged because it will not cycle on and

off normally.

To protect the air conditioner from overloading, the outdoor unit will not start running for 3 minutes

after power is applied or the unit is turned OFF.

a

Press the

(TEST RUN) button on the remote

controller. (Fig. 12-3)

b

Press the

(ON / OFF operation) button

to start the test run.

c

Press the

(MODE) button to select either

COOL or HEAT mode.

d

When the test run has started, “TEST” shows on

display of the remote controller.

e

During the test run, the air conditioner runs

continuously and the thermostat does not control

the system.

f

After the test run, press the

button once

again to cancel this mode and check that “TEST”

is not shown on the display.

The TEST RUN button is

used only for servicing the

air conditioner. Do not press

this button for normal

operation, or the system

may be damaged.

CAUTION

Fig. 12-1

Fig. 12-2

Power mains switch

(Power must be turned ON
at least 5 hours before
attempting test run)

ON

0765_C_I

Fig. 12-3

2057_C_I

MODE button

TEST RUN/CHECK
button

ON/OFF operation
button

Alarm message

Narrow tube service
valve (3-way valve)

Wide tube service
valve (ball valve)

Fully OPEN

Fully OPEN

1371_C_I