Fig. 6-3

6-2. Wired Remote Controller Installation

Do not supply power to

the unit or try to operate it

until the tubing and

wiring to the outdoor unit

is completed.

Do not twist the control

wiring with the power

wiring or run it in the

same metal conduit,

because this may cause

malfunction.

Install the remote control-

ler away from sources of

electrical noise.

Install a noise filter or

take other appropriate

action if electrical noise

affects the power supply

circuit of the unit.

If local codes allow, this remote controller can be

mounted using a conventional wall box for flush

mounting.

(1)

When you open the decorative cover, you will see

two gaps under the remote controller. Insert a

coin into these gaps and pry off the back case.

(Fig. 6-4)

(2)

Attach the back case with the 2 small screws

provided. Using a screwdriver, push open the cut-

outs on the back case. These holes are for

screws. Use the spacers and take care not to

tighten the screws excessively. If the back case

will not seat well, cut the spacers to a suitable

thickness. (Fig. 6-3)

(3)

Connect the remote controller wiring (2 wires)

correctly to the corresponding terminals in the

electrical component box of the indoor unit.

When wiring, do not connect

the remote controller wires

to the adjacent terminal

block for the power wiring.

Otherwise, the unit will break

down.

(4)

To finish, fit the back tabs of the case into the

remote controller and mount it.

CAUTION

6

6

6

6

6

RC

(WD)

Fig. 6-4

CAUTION

1989_C_I

Wired remote
controller

Decorative
cover

Concealed box for 1

Spacer

M4

×

25

Screws (2)

Under case
(Back case)

Gap

Coin

1990_M_I

Gap

Control panel

Advertising