Sanyo CH4242 User Manual

Page 38

Advertising
background image

4

4

4

4

4

U

S4359146

37

Fig. 3-78 shows an example of installation.

3-24. Installing the Drain Piping

(1)

Prepare a standard hard PVC pipe for the drain

and use the supplied hose band to prevent water

leaks.

The PVC pipe must be purchased separately.

When doing this, leave a gap between the drain

socket of the unit and the PVC pipe to allow the

drainage to be checked. The transparent drain

pipe allows you to check drainage. (Fig. 3-79)

Tighten the hose clamps so

their locking nuts face

upward. (Fig. 3-79)

(2)

After connecting the drain piping securely, wrap

the supplied packing and drain pipe insulator

around the pipe, then secure it with the supplied

clamps. (Fig. 3-80)

Make sure the drain pipe has a downward gradient

(1/100 or more) and that there are no water traps.

Fig. 3-78

Fig. 3-79

Fig. 3-80

Drain insulator (supplied)

Clamps (supplied)

0046_X_I

CAUTION

NOTE

Air outlet duct

Air-outlet grille

Ceiling material

Indoor unit

Bolt anchor

Suspension bolt

Air-intake duct

Air-intake grille

0785_U_I

Drain hose
(supplied)

Packing
(supplied)

Transparent part for
checking drainage

Hose band
(supplied)

Drain hose
adapter
(supplied)

Hard PVC pipe
(not supplied)

0964_X_I

Advertising