S4359146

10-4. Precautions during Brazing

Replace air inside the tube with nitrogen gas to

prevent copper oxide film from forming during the

brazing process.

Do not allow the tubing to get too hot during the

brazing process.

The nitrogen gas inside the tubing may overheat,

causing refrigerant system valves to become

damaged. Therefore allow the tubing to cool be-

tween brazings.

Fig. 10-6

Fig. 10-7

Fig. 10-8

Torque wrench

Spanner

Indoor unit

Outdoor unit

0131_C_I

Never grasp the drain or refrigerant connecting

outlets when moving the unit.

Fig. 10-9

10-5. Connecting Tubing between Indoor and

Outdoor Units

(1)

Tightly connect the indoor side refrigerant tubing

with the outdoor side tubing. (Fig. 10-6)

(2)

To fasten the flare nuts, apply specified torque as:

Table 10-1

Unit side
insulator

Insulation tape (white)

(supplied)

Seal (supplied)

Flare insulator (supplied)

Tube insulator
(not supplied)

Vinyl clamps (supplied)

Flare nut

1015_X_I

Insulation

Thickness:
Min. 5/16 in.

Wide tube

Narrow tube

Thickness:
Min. 5/16 in.

0999_C_I

Refrigerant tubing

Tightening Torque

Approx. 120 — 160 Ibs-in.

(140 — 180 kg-cm)

Approx. 300 — 360 lbs-in.

(340 — 420 kg-cm)

Approx. 870 — 1040 lbs-in.

(1000 — 1200 kg-cm)

Tube Dia.

1/4" (6.35 mm)

3/8" (9.52 mm)

3/4" (19.05 mm)

10-6. Insulating the Refrigerant Tubing

Always insulate tubes after

draining water and complet-

ing leak tests on all connec-

tion points.

To avoid condensation and water leaks, the wide tube

(gas line) must be insulated with the supplied insula-

tion materials.

Taping the flare nuts

Wind white insulation tape around the flare nuts at the

wide tube connections. Place the seal (supplied) on

the unit. Then cover up the tubing connections with the

flare nut insulator, and cover the gap at the union with

the supplied black insulation tape. Finally, fix the

insulator at both ends with vinyl clamps. (Fig. 10-8)

Insulation material

The material used for insulation must have good

insuIation characteristics, be easy to use, be age

resistant, and must not easily absorb moisture.

After a tube has been insu-

lated, never try to bend it

into a narrow curve because

it can cause the tube to

break or crack.

CAUTION

Important

CAUTION

Seal

Flare
insulator

Vinyl
clamp

Insulation
tape

Refrigerant tubing and insulator
(not supplied)

Drain pipe and insulator
(not supplied)

Drain insulator
and clamp.
Large
(supplied)

Packing
clamp.
Small
hose band
(supplied)