failure

Fault with
comp. and its
circuit

Possible Cause of Malfunction

Indoor thermistor is either open
or damaged.

Outdoor thermistor is either
open or damaged.

Protective device for comp. is
activated.

EEPROM (ICB of PCB) failure

Model setting of indoor unit is not matching the outdoor unit.

When using group control, main indoor unit address setting is duplicated.
(Judging by indoor unit.)

Outdoor unit address (R.C. No.) is duplicated.

Priority setting of indoor unit is duplicated.

Improper wiring between indoor units.

(There is group connection wiring in case of individual control.)

Capacity code of indoor unit is not set.

Improper wiring of group control wiring.

Possible cause of Malfunction

• Indoor or outdoor unit is not working correctly.
• Control lines between indoor unit, outdoor unit, and system
controller are not wired correctly.

• Same as for C05, above.
• Connector CN1 is not connected correctly.

When using wireless remote controller or system controller,
connect wired remote controller with the indoor unit temporarily
to check the alarm message in detail.

System controller is transmitting
incorrect signal.

System controller is detecting
incorrect signal.

Protective device of the sub-
indoor unit is activated in group
contorl.

• Serial

commu-
nication
errors

• Mis-setting

Activation of
protective
device

Possible Cause of Malfunction (The following messages are displayed only for the system controller.)

R.C.

: Refrigerant Circuit

comp. :

Compressor

temp. :

Temperature

PCB

: Printed Circuit Board

NOTE

Alarm
message

F1

F2

F3

F10

F4

F25

F7

F29

H1

H2

H3

F27

H18

Alarm
message

L2

L3

L4

L5

L6

L7

L9

L11

Indoor coil temp. (E1 = TH1) cannot be detected.

Indoor coil temp. (E2 = TH2) cannot be detected.

Indoor coil temp. (E3 = TH3) cannot be detected.

Indoor room (air-intake) temp. can not be detected.

Discharge gas temp. (comp. = TH0A) cannot be detected.

Outdoor coil gas temp. (C2 = TH0C) cannot be detected.

Outdoor coil liquid temp. (C1 = TH0D) cannot be detected.

Comp. motor is overloaded.

Comp. motor is locked.

Current of comp. cannot be detected when it is turned on.

Current of comp. is detected when it is not operated.

Comp. contactor (Mg SW) is chattering.

Alarm
message

C05

C06

P30