Charging additional refrigerant

Charge additional refrigerant (calculated from the

narrow tube length as shown in Sec. 1-5) using the

wide tube service valve with the system in cooling

operating mode. (Fig. 11-5)

Use a balance to measure the refrigerant accu-

rately.

Finishing the job

(1)

With a hex wrench, turn the narrow tube service

valve stem counterclockwise to fully open the

valve. (Fig. 11-6)

(2)

With a screwdriver, turn the wide tube service

valve stem counterclockwise to fully open the

valve. (Fig. 11-6)

To avoid gas from leaking

when removing the charge

hose, make sure the stem

of the wide tube is turned

all the way out (“BACK

SEAT” position).

(3)

Loosen the charge hose connected to the wide

tube service port (1/4 in.) slightly to release the

pressure, then remove the hose.

(4)

Replace the 1/4 in. flare nut and its bonnet on the

wide tube service port and fasten the flare nut

securely with an adjustable wrench or box

wrench. This process is very important to prevent

gas from leaking from the system.

(5)

Replace the valve caps on both the wide and

narrow service valves and fasten them securely.

This completes air purging with the vacuum pump. The

air conditioner is now ready for a test run.

Fig. 11-5

Narrow tube

Hex wrench

CLOSE

OPEN

Wide tube

1002_C_I

Fig. 11-6

CAUTION

Outdoor
unit

Wide tube

165 ft.

Narrow tube

Max. allowable
tubing length
at shipment

Required
additional
charge

Indoor
unit

1396_M_I

Advertising
This manual is related to the following products: