Sanyo CH4242 User Manual

Page 89

Advertising
background image

88

S4359146

12-4. Automatic Address Setting Method

— For group control and central control with multiple

outdoor units —

Carry out automatic address setting with the

remote controller.

(1)

All auto. address operation

1

Press the

and

(

) buttons at

the same time for more than 4 seconds.

2

Press the

button after confirming the

CODE No. AA (CODE No. AA: All Auto.

address operation).

After addresses are automatically set in

order for the outdoor units from No. 1 to No.

30, the system returns to the normal

stopped state.

(2)

Individual auto. address operation for each

refrigerant circuit

1

To select each refrigerant circuit individually

and set addresses automatically, press the

and

(

) buttons at the same

time for more than 4 seconds, then press

the

,

( ) button once to set

CODE No. A1.

(CODE No. A1: Auto. address operation)

2

Select R.C. No. which you want to execute

the auto. address operation with

button.

3

Press the

button. The auto. address

operation will start. CODE No. changes from

flashing to ON state.

4

If the error is happened during the operation,

the alarm message will display. Check and

remove the cause. If you want to interrupt

the operation, press the

button then the

unit stands in waiting mode (Press the

button).

5

If the auto. address operation finishes, the

display will disappear.

6

Execute the operation of the other R.C. line

in the same way by following the above

steps

2

to

3

.

7

Complete the auto. address operation by

pressing the

button.

Required time for auto. address operation:

In case of group control : a few minutes for each R.C.

In case of central control : max. about 20 min. for

each R.C.

12-5. Displaying Indoor / Outdoor Unit Combina-

tion Numbers

Display the indoor / outdoor unit address after auto-

matic address setting.

(1)

When installing multiple units, match the indoor

unit address numbers and the outdoor R.C.

address numbers and display them at an easy-to-

check location (near the nameplate) with an oil-

based magic marker or other indelible marker so

that the individual indoor and outdoor unit combi-

nations can be checked.

Example:

Outdoor Unit 1 – Indoor Units 1-1, 1-2, 1-3, ....

Outdoor Unit 2 – Indoor Units 2-1, 2-2, 2-3, ....

(2)

This is necessary for maintenance. Always label

these.

*Check indoor unit address with the remote

controller. Press the

button for at least 4

seconds and check the indoor unit address with

the

button. (Each time you press the

button, the address changes 1-1, 1-2, ...

2-1, 2-2, ...) The fan for only the selected indoor

unit turns on at high speed, so check which

indoor unit runs and label the indoor unit address.

(If there is 1 outdoor unit, the addresses are 1-1,

1-2, ...)

When you press the

button again, the system

returns to normal remote control mode.

NOTE

Advertising
This manual is related to the following products: