5. ELECTRICAL WIRING

5-1. General Precautions on Wiring

(1) Before wiring, confirm the rated voltage of the

unit as shown on its nameplate, then carry out
the wiring closely following the wiring diagram.

(2) Provide a power outlet to be used exclusively for

each unit, and a power supply disconnect and
circuit breaker for overcurrent protection should
be provided in the exclusive line.

(3) To prevent possible hazards from insulation

failure, the unit must be grounded.

(4) Each wiring connection must be done in accor-

dance with the wiring system diagram. Wrong
wiring may cause the unit to misoperate or
become damaged.

(5) Do not allow wiring to touch the refrigerant tubing,

compressor, or any moving parts of the fan.

(6) Unauthorized changes in the internal wiring can

be very dangerous. The manufacturer will
accept no responsibility for any damage or
misoperation that occurs as a result of such
unauthorized changes.

(7) Regulations on wire diameters differ from locality to

locality. For field wiring rules, must follow your

LOCAL ELECTRICAL CODES before beginning.

You must ensure that installation complies with all

relevant rules and regulations.

(8) To prevent malfunction of the air conditioner

caused by electrical noise, care must be taken

when wiring as follows:

The remote control wiring and the inter-unit

control wiring should be wired apart from the

inter-unit power wiring.

Use shielded wires for inter-unit control wiring

between units and ground the shield on both

sides.

(9) If the power supply cord of this appliance is

damaged, it must be replaced by a repair shop

appointed by the manufacture, because special

purpose tools are required.

(10) All wiring must be used class 1.

Model Name

(A) Power Supply

Power Supply Terminal Base

Capacity Max. Wire Diameter

CH2442

3/4 in.

25 A

50 A

AWG #6

1-1/4 in.

CH3642

3/4 in.

35 A/40 A (230/208 V)

50 A

AWG #6

1-1/4 in.

CH4242

3/4 in.

45 A

50 A

AWG #6

1-1/4 in.

Trade size
of Conduit

Trade size
of Conduit

MOP

(Fuse or HACR

type circuit braker)

AWG #12

Max. length 69 ft.

AWG #12

Max. length 69 ft.

AWG #10

Max. length 67 ft.

(C) Inter-Unit Control Wiring

(D) Remote Control Wiring

(E) Control Wiring For Group Control

AWG #18 (0.75 mm

2

)

AWG #18* (0.75 mm

2

)

AWG #18*

2

(0.75 mm

2

)

Use high voltage wire (300 V)

*1

Max. 3,300 ft.

Max. 1,650 ft.

Max. 1,650 ft. (Total)

NOTE

*

1

With ring type wire terminal.

*

2

Wire joint connection.

Control Wiring

Type

Trade size
of Conduit

Trade size
of Conduit

Indoor Unit

(B) Power Supply

Power Supply Terminal Base

Capacity Max. Wire Diameter

X, K, T, U

Max. length 330 ft.

3/4 in.

15 A

25 A

AWG #10

3/4 in.

MOP

(Fuse or HACR

type circuit braker)

5-2. Recommended Wire Length and Wire Diameter for Power Supply System

Must follow LOCAL ELECTRICAL CODES for wiring.