9-2. Electrical Wiring

B1

Indoor unit PCB

CRV
(CN91: WHT)

2P terminal base

Indoor unit

System controller

Accessary connector

Wire joint connection

2044_M_I

B2

B3

B4

B5

B6

U1

U2

How to connect electrical wiring

(1)

Connect B1, B2 to indoor PCB CRV connector
using accessary 2P connector. (*No polarity)
Total wire legth is less than 985 ft. and size is
AWG#18.

(2)

Connect B5, B6 to indoor unit 2P terminal base.
(*No polarity). Wire size is AWG#18.

Basic wiring

B1:

B2:

B3:

Not be used

B4:

Auxiliary of inter-unit control wiring

B5:

B6:

Terminals for remote monitoring

A1:

Input for turning on air conditioners concurrently.

A2:

Input for turning off air conditioners concurrently.

A3:

Common input for turning air conditioners on or off.

A4:

On operation state indicator output.

A5:

Alarm indicator output.

A6:

Common indicator output.

Basic wiring diagram of control wiring

Max. 64 indoor units and 30 outdoor units can be
connected in 1 system.

Up to 10 system controller can be connected in 1
system.

Fig. 9-3

Power supply: DC12V *No polarity
To CRV connector (CN91) on indoor PCB

Inter-unit control wiring. (Low voltage)
To indoor unit 2P terminal base (U1, U2)
*No polarity

Inter-unit
control wiring

System controller

RC1

1-1

2045_M_I

RC2

RC3

1-2

1-3

2-1

2-2

2-3

3-1

Fig. 9-4

A1

<Back side of system controller>

A2

A3

A4

A5

A6

B6

B5

B4

B3

B2

B1

Connector for
weekly timer
(Under the terminal)

3005_M_I