Sanyo CH4242 User Manual

Page 39

Advertising
background image

4

4

4

4

4

U

38

S4359146

Do not install an air

bleeder as this may

cause water to spray

from the drain pipe

outlet. (Fig. 3-81)

If it is necessary to increase the height of the

drain pipe, the section directly after the connec-

tion port can be raised a maximum of 19-11/16 in.

Do not raise it any higher than 19-11/16 in., as

this could result in water leaks.

(Fig. 3-82)

Do not install the pipe with an upward gradient

from the connection port. This will cause the

drain water to flow backward and leak when the

unit is not operating. (Fig. 3-83)

Do not apply force to the piping on the unit side

when connecting the drain pipe. The pipe

should not be allowed to hang unsupported

from its connection to the unit. Fasten the pipe

to a wall, frame, or other support as close to the

unit as possible. (Fig. 3-84)

Fig. 3-81

CAUTION

3-25. Checking the Drainage

After wiring and drain piping are completed, use the

following procedure to check that the water will drain

smoothly. For this, prepare a bucket and wiping cloth

to catch and wipe up spilled water.

(1)

Connect power to the power terminal board (L1,

L2 terminal) inside the electrical component box.

(2)

Remove the tube cover and through the opening,

slowly pour about 43 oz. of water into the drain

pan to check drainage.

(3)

Short the check pin (CN5 white) on the indoor

control board and operate the drain pump. Check

the water flow and see if there is any leakage.

Be careful since the fan will

start when you short the pin

on the indoor control board.

(4)

When the check of drainage is complete, open

the check pin (CN5 white) and remount the

insulator and drain cap onto the drain inspection

port.

To mount the tube cover,

use 5/16" (4

ЧЧЧЧЧ

8 mm) tapping

screws.

Do not use long screws as

they may puncture the drain

pan and cause water leak-

age.

1593_U_I

Air bleeder

Not good

Fig. 3-82

Fig. 3-83

Fig. 3-84

1596_U_I

Good

Support pieces

1595_U_I

No good

Upward gradient

CAUTION

CAUTION

1979_U_I

Good

11-13/16 in. or less

19-11/16 in. or less

Advertising