9-6. Connection with Other Equipments

2055_M_I

ON/OFF

Digital input

Alarm

Output common

CPEV

AWG#16

ALL ON (+)

CX

TX

ALL OFF (+)

Input common

COM

+24

CPEV

AWG#16

Name

Digital input/output terminals

Input/output item

Control input

Status output

ON/OFF output
Alarm output
Potential tree
A contact, static
(relay output)

Wire length:
less than 330 ft.

Input/output

System controller

Equipment

Input/output

Terminal

Terminal

Example

All ON input
All OFF input
Pulse (photo
compler input)

Contact capacity
DC 24V, 10mA

Pulse width:
more than
984 ft./sec.
Wire length:
less than 330 ft.

Contact capacity
DC 30V, 0.5A

9-7. Memory Back Up Switch

Check the back up switch is ON for back side of PCB

by system controller.

2056_M_I

Back up switch

ON

OFF

Back up battery

9-8. Test Run

(1)

Power on for all indoor units. Next, power on for
system controller.

will flash, checking the indoor unit address

automatically.

(2)

If group No. displayed on system controller is not
same as indoor unit No.* which is connected, see
Fig. 9-5 and setting again.

*In case of group control, main unit No. only.