Sanyo CH4242 User Manual

Page 13

Advertising
background image

12

S4359146

Air discharge

0426_C_I

Recommended outer dimensions of wind shield

(field supply)

0936_C_I

3 - ø1-9/16" hole

6 - ø15/64" hole

9-27/32"

21-5/8"

15/16"

5-3/16"

22-7/16"

1/2"

23-15/32"

21-13/16"

5-5/32"

9-27/32"

9-27/32"

1-7/32"

21-13/16"

2-1.

Air Discharge Chamber for Top Discharge

Install the air-discharge chamber in the field when:

it is difficult to keep a space of minimum 2 ft.

between the air-discharge outlet and the obstacle.

the air-discharge outlet is facing the sidewalk and

discharge hot air can annoy the passers-by.

Refer to Fig. 2-4.

2-2.

Installing the Outdoor Unit in Heavy Snow

Areas

In locations subject to strong winds, snow-proof

ducting should be fitted and direct exposure to the

wind should be avoided as much as possible.

The following problems may occur when the outdoor

unit is not provided with a platform and snow-proof

ducting.

a)

The outdoor fan may not run and there may be

damage to the unit

b)

There may be no air flow.

c)

The tubing may freeze and burst.

d)

The condenser pressure may drop because of

strong wind, and the indoor unit may freeze.

Fig. 2-4

1352_C_I

3-ø2-3/8" hole

8-ø1/4" hole

5-3/16"

5-5/32"

23-5/16"

9-7/8"

9-7/8"

17-3/4"

3-15/16"

43-15/16"

11-13/16"

22-5/16"

CH3642

CH2442

Advertising